Summary of Contents for AC Pro ACAT24F/NaA

  • Page 1 Owner's Manual Original Instructions Conditioners A-Coils Models: ACAT24F/NaA ACAT36F/NaA ACAT48H/NaA ACAT60H/NaA...
  • Page 2 To Users Thank you for selecting AC PRO’s product. Please read this instruction manual carefully before installing and using the product, so as to master and correctly use the product. In order to guide you to correctly install and use our product and achieve...
  • Page 3 If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard. (8) AC PRO assumes no responsibility for personal injury, property loss or equipment damage caused by improper installation and commissioning, unnecessary maintenance, or not following relevant national rules and regulations, industrial standards and requirements in this instruction manual.
  • Page 4: Table Of Contents

    Contents 1 Safety Precautions ..............1 2 Product Introduction ............. 2 2.1 Product Description ..............2 2.2 Optional Accessories..............2 2.3 Physical Dimension ..............3 2.4 Names of Main Parts ..............3 2.5 General Information ..............4 3 General ................... 4 4 Installation ................
  • Page 5: Safety Precautions

    A-Coils 1 Safety Precautions This product can’t be installed at corrosive, inflammable or explosive environment or the place with special requirements, such as kitchen. Otherwise, it will affect the normal operation or shorten the service life of the unit, or even cause fire hazard or serious injury.
  • Page 6: Product Introduction

    2 Product Introduction 2.1 Product Description The AC PRO A-Coil offers the perfect combination of superior product quality, operating efficiency, operating sound levels and value for money. The evaporator unit uses the environmentally friendly refrigerant R410A, which is chlorine-free to help prevent damage to the ozone layer.
  • Page 7: Physical Dimension

    A-Coils 2.3 Physical Dimension Unit: inch Dimension Model ACAT24 & 36 17-1/2 21-1/4 15-7/8 19-3/8 ACAT48 & 60 24-1/2 21-1/4 28-1/2 22-7/8 19-3/8 2.4 Names of Main Parts...
  • Page 8: General Information

    A-Coils 2.5 General Information Cooling capacity range as shown below: Model Cooling capacity(ton) ACAT24F/NaA ACAT36F/NaA ACAT48H/NaA ACAT60H/NaA 3 General The evaporator of indoor unit is charged with refrigerant in factory for pressure maintaining. The cut-off valve can be opened only when installation and vacuuming is done.
  • Page 9: Location

    In installations that may lead to physical damage (i.e. a garage) it is advised to install a protective barrier to prevent such damage. 4.3 Piping Work 4.3.1 Specification of Connection Pipe External diameter (inch) Model Gas pipe Liquid pipe ACAT24F/NaA ACAT36F/NaA Φ3/4 Φ3/8 ACAT48H/NaA ACAT60H/NaA...
  • Page 10: Condensate Removal

    A-Coils 4.3.2 Piping Preparation 4.3.2.1 Solder Connection All cut ends are to be round, burr free, and cleaned. Failure to follow this practice increases the chances for refrigerant leakage. 4.3.2.2 Screw Connection Pipe diameter (inch) Tightening torque (N·m) Φ1/4 15-30 Φ3/8 35-40 Φ1/2...
  • Page 11: Ductwork

    A-Coils Condensate drain pipe should be connected into special drain system for air conditioner. The drain pan has primary and secondary drain connection. Condensate removal is performed by attaching a 3/4” PVC pipe to the evaporator coil pan and terminated in accordance with local or state Plumbing/HVAC codes. The installation must include a “P”...
  • Page 12: Unit Installation

    A-Coils 4.6 Unit Installation Risk of explosion or fire. Can cause injury or death. Install the furnace or air handler and condensing unit according to the installation instructions provided with the unit. Position the cased coil on top of the furnace or air handler cabinet and secure it using field-provided screws.
  • Page 13: Blower Speed Selection

    300-450 CFM per 12,000 Btu/h of cooling capacity (wet coil). Recommended air flow volume as shown in Table 1. Table 1 Cabinet Recommended Vol(CFM) Model Width(in.) ACAT24F/NaA 17.5 ACAT36F/NaA 17.5 1000 ACAT48H/NaA 24.5 1230 ACAT60H/NaA 24.5...
  • Page 14: After-Sales Service

    A-Coils 7 After-Sales Service In case the air-conditioning unit you bought has any quality problem or you have any inquiry, please contact the local after-sales service agency designated by factory. Warranty should meet the following requirements: First run of the unit should be operated by professional personnel from factory appointed service center.
  • Page 16 Add: 11700 Industry Ave., Fontana, CA 92337, USA Tel: 1-951-360-0630 E -mail: www.acpro.com...

This manual is also suitable for:

Acat36f/naaAcat48h/naaAcat60h/naa