CUTTING THE FLUE COMPONENTS

The flue components can be sharp, CARE is to be taken when handling to avoid injury.
CAUTION
Referring to "Flue Component Dimensions" on page
13, calculate the required number and type of flue
components that are needed to reach from the water
heater to the flue terminal.
The grey plastic inner pipe should always extend 10mm
beyond the white outer pipe on the male end of the flue
pipe.
When cutting flue components ONLY the MALE end
is to be cut, DO NOT attempt to cut the female end.
Flue pipe components overlap by 32 mm. Therefore
when cutting to length, add 65 mm to the flue pipe
length (X) needed for installation. See Fig. 1.
Cutting flue components can create sharp edges, care must be taken to avoid injury, use a file to
remove debris, burrs and sharp edges from cut ends.
IMPORTANT
Ends that are left unfinished can damage the flue seals and result in the flue components no
longer being air or weather tight.
The ONLY COMPONENTS that can be cut are as follows: FFPPWALLKIT (pipe not bend),
FFPPPIPE1000, FFPPROOFCOWL and UVROOF PROTECTORS.
Ensure all ends are cut square (the use of a mitre box will ensure a clean square cut).

LUBRICATING COMPONENTS

A container of "O" ring lubricant is provided with every termination, the contents of which is sufficient to install the
flue system. To ease assembly, lubricate the "O" rings of the inner pipes of each flue component prior to assembly.
Use only a water based "O" ring seal lubricant. DO NOT use petroleum based lubricants such as
petroleum jelly, as such products may cause deterioration.
IMPORTANT
APPLIANCE SPIGOT DIMENSIONS & CENTRES
The wall mounting brackets are fixed.
The spigot centre is a fixed 155mm relative to the wall mounting surface. See Fig. 2 for all spigot related dimensions.
A
Item
is NOT a condensate drain connection and MUST remained capped at all times.
A
WARNING
Rinnai
470mm
235mm
Fig. 2
- REU-N Series spigot dimensions / connections
WARNINGS & IMPORTANT INFORMATION
x + 65 mm
32 mm
10 mm
65 mm
WHITE PLASTIC
(OUTER)
Fig. 1
155mm
A
5
When cutting
flue components
ONLY the MALE
end is to be cut!
GREY PLASTIC
(INNER)
HW_CF_FFPP_FIM