FIRE INSTRUCTION & SERVICE MANUAL
A100 Range AlertAlarm Sounder UL464 / CAN/ULC-S525
Model: A100DC
Attention: Installation must be carried out by an electrician in compliance with the National Electrical Code, NFPA 70, and the National Fire Alarm
Signaling Code, NFPA 72 or CSA 22.1 Canadian Electrical Code, Part I, Safety Standard for Electrical Installations, Section 32. / L'installation doit
exclusivement être réalisée par du personnel qualifié, conformément au code national d'électricité américain, NFPA 70, et le code national d'alarrme
incendie et de signalisation NFPA 72 ou CSA 22.1 Code canadien de l'électricité, première partie, norme de sécurité relative aux installations électriques,
Section 32
Attention: Disconnect from power source before installation or service to prevent electric shock / Débranchez-le de la source d'alimentation avant l'instal-
lation ou l'entretien pour éviter tout choc électrique.
Attention: Do not paint / Ne pas Peinturer
• -40°C to +66°C / -40°F to +151°F
• Units can be mounted using the 2-off ø6mm holes in the mounting lugs or through the back of the housing using the supplied gasket
seal.
• A100DC024 is approved for use as an audible signal appliance for fire alarm use – Public Mode (UL464 & CAN/ULC-S525) and produc-
es a minimum sound pressure level of US: 79.55dB(A); CA: 85.2dB(A) at 10 feet, (figures @ worst case 10Vdc).
• At 24Vdc the A100DC024 produces a minimum sound pressure level of US: 88.52dB(A); CA: 93.7dB(A) at 10 feet
• For Fire Alarm applications, the Sounder Volume must be at the highest setting, (see volume control section). For fire alarm use, Tone
12 as shown below must be selected:
Stage 1
Set DIP
Tone Description
SW 1
Tone No.
1000Hz(0.5s on, 0.5s off)x3 + 1s gap ISO 8201 Temporal
12
Pattern
• Connection Terminals: Pluggable
AC: 1.0 - 2.5mm
DC: 0.2 - 2.5mm
• Terminal Tightening torque 0.4Nm
• To maintain Ingress Protection, cable entries must be fitted with suitably rated cable glands or stopping plugs
• Units can be located indoor or outdoor wet use, wall or ceiling mounted and there are no limitations on orientation
• Factory finishes are not intended to be modified
Model
A100DC024
A100DC024 Sounder Directional Characteristics for Canadian Fire CAN/ULC-S525 at 10 feet
Horizontal Axis
Angle
OSPL
Ref. 90°
92.6 dB(A)
149°
-3 dB(A)
153°
-6 dB(A)
180°
87.2 dB(A)
E2S Warning Signals
2
/ AWG18 - AWG12
2
/ AWG24 - AWG12
Surge Current Ratings for use in fire alarm systems
Nominal Voltage
Voltage Range
24V dc
10 - 60V dc
Angle
Ref. 90°
92.6 dB(A)
32°
28°
+ + - - S2 S3
Impress House, Mansell Road, Acton, London W3 7QH
Tone Visual
1000Hz 0.5s
0.5s
0.5s
0.5s
0.5s
Initial Peak
298mA
OSPL
Angle
Ref. 90°
-3 dB(A)
148°
-6 dB(A)
151.5°
87 dB(A)
180°
S2
S1
sales@e2s.com
Stage 1 & 2
Stage 3
DIP SW 1/2
Set DIP
Settings
1 2 3 4 5 6
1 1 0 1 0 0
1s
Vertical Axis
OSPL
Angle
93 dB(A)
Ref. 90°
-3 dB(A)
33°
-6 dB(A)
29°
87.2 dB(A)
e2s.com
D218-00-001-IS-UL Issue A 26/04/2021
Stage 4
Set DIP
SW 1
SW 1
(S3)
(S2 + S3)
1
8
Initial RMS
56.4mA
OSPL
93 dB(A)
-3 dB(A)
-6 dB(A)
86.4 dB(A)