Samsung MH020FPEA Service Manual page 198

Multi air conditioner
Hide thumbs Also See for MH020FPEA:
Table of Contents

Advertisement

15-2 Technical Document (Pressure Graph)
15-2-1 MH052FXEA2(MH040FXEA2/MH14✳✳2X/MH16✳✳2X/MH18✳✳2X/MH19✳✳2X refer to the 100% combination)
I
Cooling(7.5m–Piping)
Outdoor
Indoor
P_high
21
21.10
21
27
22.00
32
22.90
21
31.29
35
27
32.50
32
33.06
21
37.50
43
27
38.20
32
39.40
Samsung Electronics
135% (ex. 035+035)
P_low
T_dis
T_suc
8.60
61.40
8.70
9.50
59.50
11.30
10.65
58.50
14.30
8.00
84.30
6.50
9.10
84.80
8.90
10.50
82.00
13.80
8.20
94.20
7.30
9.40
94.30
10.70
10.70
92.40
14.40
100% (ex. 026+026)
P_high
P_low
T_dis
19.60
8.00
58.30
21.00
8.78
59.30
22.20
10.11
58.70
27.70
8.08
79.00
28.10
9.20
77.30
28.90
10.58
74.30
34.70
8.10
93.10
35.50
9.20
91.10
36.10
10.80
88.10
T_suc
7.40
9.30
12.90
7.30
11.30
14.13
7.30
10.33
14.60
15-2