2. The equipment is not capable of withstanding the 500 V electrical
strength test as defined in clause 6.3.13 of EN 60079-11:2012. This
must be taken into account during installation.
3. The measured capacitance between the equipment enclosure and
metallic conduit adapter is 21pF. This must be considered only when
the Model 781S is integrated into a system where the process
connection is not grounded.
6.9
International
I7 IECEx Intrinsic Safety
Certificate IECEx BAS.20.0021X
Markings
Standards IEC 60079-0: 2017, IEC 60079-11: 2011
Special Conditions for Safe Use (X):
1. The plastic enclosure may constitute a potential electrostatic ignition
risk and must not be rubbed or cleaned with a dry cloth.
2. The equipment is not capable of withstanding the 500 V dielectric
strength test as defined in clause 6.3.13 of IEC 60079-11: 2011. This
must be taken into account during installation.
3. The measured capacitance between the equipment enclosure and
metallic conduit adapter is 21pF. This must be considered only when
the Model 781S is integrated into a system where the process
connection is not grounded.
Quick Start Guide
Ex ia IIC T4 Ga (–40 °C ≤ Ta ≤ +70 °C), Ex ic IIC T4 Gc (–40 °C ≤
Ta ≤ +70 °C)
Quick Start Guide