DIEL MT 200 E Installation And Instruction Manual page 28

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 18
A: ALARM (Usually used for network
release), default 160
FAN1 is proposed, as enabled default, to
disable the ventilation control, set the value
of the first display to 0 with the keys
and press
L: FANS SHUTDOWN, default 90 (if FAN1
enabled)
H: FANS IGNITION, default 100
(if FAN1 enabled)
The control unit will cyclically propose the values to be set for each channel, at
the end the settings of the common values of the control unit will follow
C: PROTECTION OF FAN BEARINGS,
default 1, C=0 not active, C=1 fan ignition
once a day 5 min, C=2 fan ignition once a
week 5 min
At the end of the programming cycle, the control unit performs the test on all
the light sectors and positions itself in the main menu displaying the maximum
measured temperature and the relative channel.
For safety reasons, the time required for programming is in any case checked.
Over one minute from the start of the programming phase, the same is
interrupted and not saved (therefore the previously set parameters remain
active) after which it returns to automatic display mode.
MT 200 E
to confirm.
THERMOMETRIC PROBES DIAGNOSTICS
PROBE INTERRUPTED: FAULT relay switching,
display flashing, letters "ICF" display with relative
channel number and FAULT led lighting.
PROBE IN SHORT CIRCUIT: FAULT relay
switching, display flashing, letters "SCF" display
- 28 -
ENG