4.2.
Error diagnosis
Problem displayed on the alarm panel
Non-zero measurement
Non-zero measurement in the absence of gas.
Measurement too high or too low
Zero measurement in the presence of gas.
"Fault" signal active on the panel
4.3.
Spare parts and accessories
Spare parts
Card D•BASE 3F+ with catalytic sensor CH
Card D•BASE 3F+ with catalytic sensor C
Card D•BASE 3F+ with catalytic sensor C
Cover without face for detector D•Tex3F & D•Can
Accessories
Remote gas injection kit D•LINE
Airtight protection kit IP65 D•LINE
Collector cover D•LINE
Airtight remote gas measurement kit D•LINE
www.dalemans.com
Possible cause(s)
▪
Presence of gas possible.
▪
Detector calibration fault.
▪
Wiring or connection defective.
▪
Voltage in the detector (between the "24V"
and "GND" terminals) outside of limits.
▪
Sensor or filter obstructed (dust).
▪
Sensor or filter contaminated. Replace the
sensor AND the filter.
▪
Wiring or connection defective.
▪
Sensor disconnected or defective.
Voltage in the detector (between the "24V"
▪
and "GND" terminals) outside of limits.
100% LEL
4
H
100% LEL
3
8
H
100% LEL
4
10
Reference
BASDLINE031
BASDLINE032
BASDLINE033
BOI00000237
Reference
ACCKIT00006
ACCKIT00007
ACCKIT00008
ACCKIT00009
|
15