Lucent Technologies LINEAGE 2000 FPS Product Manual
Lucent Technologies LINEAGE 2000 FPS Product Manual

Lucent Technologies LINEAGE 2000 FPS Product Manual

Flexible power system monitor and control unit

Advertisement

Quick Links

Product Manual
167-790-048
Comcode 107044471
Issue 4
August 1996
©1996 Lucent Technologies
All Rights Reserved
Printed in U.S.A.
Flexible Power System
Monitor and Control Unit
Notice:
Every effort was made to ensure that the information in this
document was complete and accurate at the time of printing.
However, information is subject to change.
Lucent Technologies
LINEAGE
®
2000

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the LINEAGE 2000 FPS and is the answer not in the manual?

Questions and answers

Summary of Contents for Lucent Technologies LINEAGE 2000 FPS

  • Page 1 Monitor and Control Unit Notice: Every effort was made to ensure that the information in this document was complete and accurate at the time of printing. However, information is subject to change. ©1996 Lucent Technologies All Rights Reserved Printed in U.S.A.
  • Page 2: Table Of Contents

    Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit Table of Contents 1 Introduction General Information 1 - 1 Technical Support 1 - 3 USA, Canada, Puerto Rico, and the US Virgin Islands 1 - 3 Central and South America...
  • Page 3 Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit 4 Acceptance Testing LED Test 4 - 1 Meter Accuracy 4 - 2 Battery on Discharge (115C only) 4 - 2 Fuse Alarm Test 4 - 3 On/Standby Test 4 - 4...
  • Page 4 Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit List of Figures Figure 1-1: Monitor and Control Unit For Flexible Power System 1 - 5 Figure 1-2: Monitor and Control Unit For Flexible Power System (Block Diagram) 1 - 6...
  • Page 5 Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit List of Tables Table 1-A: Feature Summary 1 - 2 Table 2-A: 115B and 115C Monitor and Control Unit Specifications 2 - 1 Table 2-B: BD Voltage 2 - 5...
  • Page 6: Introduction

    Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit Introduction General This product manual (167-790-048) describes the 115B and 115C Monitor and Control Units used in the Lucent Information Technologies Lineage® 2000 Flexible Power System (FPS). The FPS consists of the Lucent Technologies Lineage® 2000 Small Converter Plant (SCP) and the Lineage®...
  • Page 7 Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit Table 1-A: Feature Summary Small Converter Plant (SCP) (115B) Converter Features Converter Voltage Monitoring Converter Current Monitoring Converter Voltage Adjust Converter Voltage Measurable by ECS CP3 Converter Current Measurable by ECS CP3...
  • Page 8: Technical Support

    Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit The 115C Monitor and Control Unit is shown in Figure 1-1. Figure 1-2 is a block diagram of the 115 Monitor and Control Unit. It shows the various alarm gathering and reporting...
  • Page 9: Product Repair And Return

    Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit Product Repair Repair and return service for Lucent Technologies Technologies equipment is available to customers around the world. and Return USA, Canada, For information on returning of products for repair, customers Puerto Rico, and may call 1-800-255-1402 for assistance.
  • Page 10 Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit Figure 1-1: Monitor and Control Unit For Flexible Power System Issue 4 August 1996 Introduction 1 - 5...
  • Page 11 Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit CONVERTERS OR RECTIFIERS RECT CONV BATTERY TERMINATION PANEL LAMP TEST AND VOLTAGE/CURRENT OUTPUT VOLTAGE ON/STANDBY MONITORING ADJUST METER REMOTE ACCESS 3 1/2 DIGIT LCD INTERFACE FPS REMOTE ACCESS DISTRIBUTION RECTIFIER...
  • Page 12: Product Description

    Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit Product Description Monitor and Control Unit Specifications Table 2-A: 115B and 115C Monitor and Control Unit Specifications 115B 115C Operating Voltage: 19 VDC to 30 VDC 38 VDC to 72 VDC Input Power: 3.5 watts max...
  • Page 13: Feature Description

    Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit Table 2-A: 115B and 115C Monitor and Control Unit Specifications ECS Controller Datalogger Range: 0 to 6V (for monitoring Outputs: plant voltage) Range: 0 to 6V (for monitoring plant current) Voltage Accuracy: +/-1.5% of reading...
  • Page 14 Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit Alarm Condition for Alarm Code 115B Power Major (PMJ) Two or more converters alarm or go on/standby. (Also creates a PMN alarm.) Power Minor (PMN) One converter alarms or goes on/standby.
  • Page 15 Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit Adjustable The Battery on Discharge (BD) alarm is provided for a SRCP Battery on plant equipped with backup batteries. In the event that AC power Discharge Alarm is lost, the batteries provide power for a period of time to allow maintenance personnel to correct the problem.
  • Page 16 Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit Table 2-B: BD Voltage O = Switch Open, C = Switch Closed Voltage 440A 440B 440C 440D 440E 440F Notes (.5V) (1V) (2V) (4V) (8V) (24/48) 23.0 +.25V 23.5 +.25V 24.0 +.25V...
  • Page 17: Ac Fail

    Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit AC Fail The AC Fail Alarm, which is only provided on the 115C, is intended to indicate that ac input power to at least one rectifier has disappeared or dropped below a minimum voltage. This alarm is provided as an isolated transfer contact for the office alarm systems.
  • Page 18: Front Panel Meter

    Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit Front Panel A 3-1/2 digit, backlit liquid-crystal display is located on the front Meter of the Monitor and Control Unit. A switch near the display selects either the plant voltage or the plant current to be shown.
  • Page 19: Front Panel Test Jacks

    Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit Front Panel Test Test points are provided on the front panel so that the plant Jacks voltage may be checked with the user' s meter. The test points are current-limited against accidental short circuits by test probes. In the 115B, the converter output voltage is brought out to the test points.
  • Page 20 Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit Table 2-C: Alarm and Control Signals 1 BATT 1 BD - NO 2 AUX - PMJ 2 BD-C 3 AUX - PMN 3 BD-NC 4 PMJ - NO 5 CONV O/S...
  • Page 21: Installation And Setup

    Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit Installation and Setup This section covers the installation and setup procedures for the 115B and 115C Monitor and Control Units. Follow all the applicable steps in the following sections in the order they are presented.
  • Page 22: Hardware Setup

    Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit Hardware Setup Caution Circuit packs can be damaged by static electricity. Operators should always wear a grounded wrist strap plugged into the shelf when touching or handling circuit packs. Battery on...
  • Page 23 Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit 1. Refer to Table 2-C or the label near the terminals for terminal assignments. 2. The terminal blocks accept the stripped (.25 inch) ends of 22-24 AWG stranded wire. Wires should be strain relieved on the tie bar just behind the terminal block area.
  • Page 24: Acceptance Testing

    Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit Acceptance Testing The Monitor and Control Unit is tested as a unit and as part of a Flexible Power System in the factory. This section of the manual is provided for those users who wish to repeat some of those test procedures as part of the installation and turn-up process.
  • Page 25: Meter Accuracy

    Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit 115B 115C Normal Green Normal Green Yellow Yellow Yellow Verify that all of the LEDs in each rectifier and/or converter in the FPS are also lit while the LED Test button is pressed.
  • Page 26: Fuse Alarm Test

    Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit Step E: Verify that the BD LED is lit and Normal LED is extinguished. Step F: Using the ohms scale on the DMM, measure an open between TB4-2 and TB4-1 and a short between TB4-2 and TB4-...
  • Page 27: On/Standby Test

    Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit Step F: Verify that the Normal LED is lit and that the PMJ and BD LEDs are extinguished. On/Standby Test For 115B: Step A: Place a short between TB3-6 and TB3-5.
  • Page 28: Voltage Adjust

    Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit Voltage Adjust For 115B: Step A: Adjust the potentiometer all the way clockwise. Step B: Verify that the plant voltage is 48V +/- .5V Step C: Adjust the potentiometer all the way counter-clockwise.
  • Page 29: Operation

    Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit Operation The front panel switches and indicators provide the only operator interaction in a 115 Monitor and Control Unit that is operating normally. In the event of a malfunction, refer to the Troubleshooting section of the shelf product manual.
  • Page 30 Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit MJF indicator: Red LED, when lit, indicates an overcurrent protector in the distribution has operated. Such protectors include circuit breakers and fuses. This is a MAJOR alarm condition. (10) PMJ indicator: Red LED, when lit, indicates multiple CFA alarms, multiple RFA alarms, BD alarm, MJF alarm, or battery temperature alarm (BNF2 circuit pack).
  • Page 31: Product Warranty

    Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit Product Warranty A. Seller warrants to Customer only, that: 1. As of the date title to Products passes, Seller will have the right to sell, transfer, and assign such Products and the title conveyed by Seller shall be good;...
  • Page 32 Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit B. The Warranty Period listed below is applicable to Seller’s Manufactured Products furnished pursuant to this Agreement, unless otherwise stated: Warranty Period Repaired Product Product Type New Product or Part*...
  • Page 33 Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit responsibility, at its expense, to make the Cable and Wire Products accessible for repair or replacement and to restore the site. Products returned for repair or replacement will be accepted by Seller only in accordance with its instructions and procedures for such returns.
  • Page 34 Lucent Technologies Lineage ® 2000 FPS Monitor and Control Unit Copyright © 1996 Lucent Technologies All Rights Reserved Printed in U.S.A. 6 - 4 Product Warranty Issue 4 August 1996...