Lucent Technologies J85568C-1 Product Manual
Lucent Technologies J85568C-1 Product Manual

Lucent Technologies J85568C-1 Product Manual

Lineage 2000 battery distribution fuse bay
Table of Contents

Advertisement

Quick Links

Product Manual
157-005-100
Comcode 106752637
Issue 4
March 1998
©1998 Lucent Technologies
All Rights Reserved
Printed in U.S.A.
Battery Distribution Fuse Bay
Notice:
The information, specifications, and procedures in this manual
are subject to change without notice. Lucent Technologies
assumes no responsibility for any errors that may appear in this
document.
Lucent Technologies
Lineage
®
2000
(BDFB)
J85568C-1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the J85568C-1 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Lucent Technologies J85568C-1

  • Page 1 Battery Distribution Fuse Bay (BDFB) J85568C-1 Notice: The information, specifications, and procedures in this manual are subject to change without notice. Lucent Technologies assumes no responsibility for any errors that may appear in this document. ©1998 Lucent Technologies All Rights Reserved...
  • Page 2: Table Of Contents

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) Table of Contents 1 Introduction General 1 - 1 Documentation 1 - 2 Additional Information 1 - 2 Technical Support 1 - 2 USA, Canada, Puerto Rico, and the US Virgin Islands 1 - 2...
  • Page 3 Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) Monitoring Multiple Alarm Modules for Positive Plants 3 - 27 Reference Data 3 - 27 4 Installation Installation Material Provided 4 - 1 Installation Material Required But Not Provided 4 - 1...
  • Page 4 Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) List of Figures Figure 1-1: J85568C-1 Battery Distribution Fuse Bay (BDFB) 1 - 5 Figure 3-1: 7-foot cabinet (List 1) 3 - 4 Figure 3-2: 7-foot cabinet (List 1, BF)
  • Page 5 Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) Figure 3-19: P101 frame power loss alarm wiring 3 - 33 Figure 3-20: Fuse alarm wiring for positive plant P101 3 - 34 Figure 4-1: BDFB Floor Footprints (Top, 7-foot Cabinet,...
  • Page 6 Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) List of Tables Table 2-A: J85568C-1 BDFB Ordering Information 2 - 1 Table 3-A: Recommended Double Hole Terminal Lugs For Terminating Input Battery And Return Cables (350 KCMIL Maximum) 3 - 15...
  • Page 7: Introduction

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) Introduction General This product manual describes the J85568C-1 Battery Distribution Fuse Bay (BDFB). The J85568C series BDFB is shown in Figure 1-1. It serves as a secondary fuse distribution center for dc power delivered from a central office battery plant to the using equipment.
  • Page 8: Documentation

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) load-bus feeds, output load leads and ground return leads. Suggested cable routing strategies for cable entry are also discussed. Documentation This document (Lucent Technologies 157-005-100) is part of a set of documentation developed to assist engineering and installation personnel.
  • Page 9: Usa, Canada, Puerto Rico, And The Us Virgin Islands

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) sales representative who will be happy to discuss your specific needs. Europe, Middle If you need product technical support, contact your local Field East, and Africa Support/Regional Technical Assistance Center or contact your sales representative who will be happy to discuss your specific needs.
  • Page 10: Help

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) Help Technical Assistance is available at any time through the Lucent Technologies Technical Hotline at 1-800-CAL-RTAC (1-800- 225-7822). For customer service, call 1-800-THE-1PWR (1- 800-843-1797). 1 - 4 Introduction Issue 4 March 1998...
  • Page 11: Figure 1-1: J85568C-1 Battery Distribution Fuse Bay (Bdfb)

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) L IN J 8 5 E AL FE ED ER BA BD FB FE ED ER BA BD FB FE ED ER BA BD FB FE ED ER BA BD FB...
  • Page 12: Ordering Information

    Ordering Information The following tables are provided to describe the list structure of the J85568C-1 BDFB. Table 2-A provides a summary of the J85568C-1 List structure and Table 2-B a summary of ED- 83127-30 Group options. A detailed description of each of the options on the BDFB is presented in Section 3.
  • Page 13 Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) Table 2-A: J85568C-1 BDFB Ordering Information Description List Optional equipment for a discharge return bus mounted to a fuse panel (maximum of one per fuse panel) Equipment always required in addition to List 20 for terminating battery return cabling to panel position 1.
  • Page 14 Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) Table 2-A: J85568C-1 BDFB Ordering Information Description List Optional material to provide a 2400 ampere discharge return bus arranged for mounting on a 15 or 20 inch ladder type cable rack...
  • Page 15: Product Description

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) Product Description General The Battery Distribution Fuse Bay (BDFB), Model J85568C-1, is available in five cabinet arrangements. These include: Description 7 foot cabinet: 26 inches wide by 15 inches deep...
  • Page 16: Features

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) Features The following is a list of the many features provided with this product: • Distributes +/- 24, 48 or 130 volt dc power • 7, 9 or 11-1/2 foot cabinet arrangements •...
  • Page 17: Cabinet Types And Features

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) J85568C-1 Cabinet Cabinet Types Two cabinet types and three cabinet extension options are and Features available with this BDFB: List 1 7 foot Cabinet List 2 9 foot Cabinet List 3 9 foot Cabinet with 2-1/2 foot Extension Cabinet...
  • Page 18: Figure 3-1: 7-Foot Cabinet (List 1)

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) LINEAGE 2000 BDFB J85568C-1 FRAME ALARM FEEDER BAY: BDFB: Digital Meters Spare Fuse Holders FEEDER BAY: CAUTION FOR CONTINUED PROTECTION AGAINST RISK OR FIRE AND SHOCK REPLACE ONLY THE SAME TYPE...
  • Page 19: Figure 3-2: 7-Foot Cabinet (List 1, Bf)

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) LINEAGE 2000 BDFB J85568C-1 FRAME ALARM FEEDER BAY: BDFB: Removable Digital Meters Riser Cover FEEDER BAY: BDFB: CAUTION FOR CONTINUED PROTECTION AGAINST RISK OR FIRE AND SHOCK REPLACE ONLY THE SAME TYPE...
  • Page 20: Figure 3-3: 9-Foot Cabinet (List 2)

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) LINEAGE 2000 BDFB J85568C-1 FRAME ALARM FEEDER BAY: BDFB: Spare Fuse Holders FEEDER BAY: BDFB: FEEDER BAY: BDFB: Digital Meters FEEDER BAY: CAUTION FOR CONTINUED PROTECTION AGAINST RISK OR FIRE AND SHOCK...
  • Page 21: Figure 3-4: 9-Foot Cabinet (List 2, Bf)

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) L I N E A G E 2 0 0 0 B D F B J85568C-1 FRAME ALARM FEEDER BAY: BDFB: Removable Riser Cover FEEDER BAY: BDFB: FEEDER BAY: BDFB:...
  • Page 22: Figure 3-5: 2-1/2-Foot Extension Cabinet

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) 9' Cabinet Frame Mounting Hardware Ground Strap Figure 3-5: 2-1/2-foot extension cabinet 3 - 8 Product Description Issue 4 March 1998...
  • Page 23: Figure 3-6: 2 Foot Or 4-1/2 Foot Extension Cabinet

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) 4-1/2' Frame Frame Mounting Mounting Hardware Hardware Ground Ground Strap Strap 7' Cabinet 7' Cabinet L u c L u c e n t e n t Figure 3-6: 2 foot or 4-1/2 foot extension cabinet Cabinets may be configured for either top or bottom cable entry.
  • Page 24: Load Bus Arrangements

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) NOTICE: Equip fuse panels starting at panel position 1 to eliminate possible cable congestion when installing additional fuse panels in the field Load Bus The bus bars used in the BDFB are sized to provide a 600 ampere Arrangements current carrying capacity for each load bus.
  • Page 25 Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) NOTICE: All bus bars used in this product are copper with a solder plate finish. Bus bars do not require buffing or the application of NO-OX before connection to terminal lugs or other bus bars.
  • Page 26: Figure 3-7: (Left) Busing Scheme To Fuse Panels Figure 3-8: (Right) Connecting Multiple Battery Buses

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) List 11 List 13 List 15 Shunt List A List A Figure 3-7: (Left) Busing scheme to fuse panels Figure 3-8: (Right) Connecting multiple battery buses 3 - 12 Product Description...
  • Page 27: Figure 3-9: (Left) Busing Scheme To Internal Discharge Returns Figure 3-10: (Right) Connecting Multiple Internal Discharge Returns

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) List 23 List 21 List 21 List 20 List 20 List B List 20 List 20 List B List 20 List 20 List 25 Figure 3-9: (Left) Busing scheme to internal discharge...
  • Page 28 Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) Discharge Two optional discharge return bus options are available for Return Bus terminating fuse return leads: (1) Bus bar returns located in the Options BDFB or (2) A return bus located outside the BDFB on a cable rack.
  • Page 29: Table 3-A: Recommended Double Hole Terminal Lugs

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) cable rack mounting hardware. List K2 provides a bus bar, the connecting bus bar and insulating standoffs for stacking additional tiers as required. List K3 provides the ED83019-50 G1 bus bar assembly, which has a 1200 ampere current rating.
  • Page 30: Figure 3-11: External Discharge Return Bus Options On Cable Rack

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) List K2 List K1 List K3 Figure 3-11: External discharge return bus options on cable rack 3 - 16 Product Description Issue 4 March 1998...
  • Page 31: Figure 3-12: Bus Bar Hole Pattern And Numbering Schemes

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) .221 Dia. on .62 Centers (24 Places) Row A for 1st Level Row B for 1st Level .437 Dia. on 1.00 Centers Row D for 2nd Level Row E for 2nd Level (25 Places) 26.00...
  • Page 32: Table 3-C: Recommended Double Hole Terminal Lugs For Terminating To External Discharge Return Bus

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) Table 3-C: Recommended Double Hole Terminal Lugs For Terminating To External Discharge Return Bus Rows B and E (Lists K1 and K2) Rows A and D (List K3) KS-5482 Wire KS-20921 Wire WP-91412 List...
  • Page 33: Table 3-D: Recommended Mounting Hardware For Securing Double Hole Terminal Lugs To External Discharge Return Bus

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) Table 3-D: Recommended Mounting Hardware For Securing Double Hole Terminal Lugs To External Discharge Return Bolt Size Comcode Quantity Description 840059885 Screw, PHM 802841510 Washer, Plain 0.190 802235127 Lockwasher 800812935...
  • Page 34: Figure 3-13: Digital Meters (Front And Back Views)

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) Stamping Area for Load Designations LOAD SELECTOR LOAD CURRENT (AMPERES) Digital Meter Display Front View 3 Position Switch Position 1 Position 1 Back View Figure 3-13: Digital meters (front and back views) ED-83127-30 Two types of fuse panels are available.
  • Page 35 Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) Group A provides one 3-70 ampere cartridge type fuse holder, comcode 406686980. This fuse block is UL listed and provides a more compact design than previous fuse holders. The fuse block was developed by USD (Underwriters Switching Devices) to accomodate the WP-92461 series of fuses.
  • Page 36: Figure 3-14: Ed83127-30 Fuse Panels

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) GMT Fuse SPARE Module SPARE FUSES FUSES (Group B) Spare Fuse Holder Fuse Block (Group A) Blank Filler (Group C) Spare Fuse Holder SPARE SPARE FUSES FUSES Group 1 Group 2...
  • Page 37: Table 3-E: Wp-92461 Cartridge Fuse Ordering Information

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) Table 3-E: WP-92461 Cartridge Fuse Ordering Information Comcode WP-92461 List Rating 406700567 406700583 406700591 406700609 406700617 406700625 406700633 406700641 406700658 406700674 406700682 406700690 402328926 .18 amp GMT alarm fuse Table 3-F: Recommended Single Hole Terminal Lugs For Terminating To ED- 83127-30 Group “A”...
  • Page 38: Alarm Circuit Module

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) Table 3-G: GMT Fuse Ordering Information Comcode Amp Rating 401231501 401841473 400994604 1-1/3 401231527 401231535 Table 3-H: Recommended T&B Lugs For Terminating GMT Load Leads And Returns Wire Size T&B Lug...
  • Page 39: Detailed Circuit Description

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) When power loss to a panel occurs, a closure exists between pins 1 and 2 and pins 3 and 4 on the output connector (P101), while an open condition exists between pins 1 and 9 and pins 3 and 10.
  • Page 40 Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) Frame Alarm In addition to the individual panel alarm indicators, there is also a frame alarm lamp at the top of the bay. This frame alarm lights when power is lost to a fuse panel or there is a fuse alarm. Power for lighting the frame lamp is brought from the battery plant on an auxiliary battery supply (ABS) lead.
  • Page 41: Monitoring Multiple Alarm Modules For Positive Plants

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) single alarm module. All packs will alarm independently by simply disconnecting pin 1. Power Loss Alarm Remote monitoring of power loss is furnished for individual fuse panels. However, power loss alarms will probably not be...
  • Page 42 Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) CR102 Diode bridge, fuse alarm CR103 Voltage blocking diode DS101 Green power LED DS102 Red fuse alarm LED 3 - 28 Product Description Issue 4 March 1998...
  • Page 43: Figure 3-15: A-Cp/Bep1 Board Layout

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) CR101 CR102 P102 P101 Figure 3-15: A-CP/BEP1 board layout Issue 4 March 1998 Product Description 3 - 29...
  • Page 44: Figure 3-16 : A-Cp/Bep1 Input/Output Connections (Alarm Module With No Power Is In "Normal" State)

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) Panel Alarm Input Connector Remote Alarm Output Connector Pins 2 and 9 send ABS to light Frame Alarm. P102 P101 K101-4 Power Loss (Aud) Fuse Alarm Signal Input (W-Y) K101-6...
  • Page 45: Figure 3-17: Frame Alarm

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) From (24, 48, or 130V) (24, 48, or 130V) Battery Plant Battery Plant Option "X" ABS RTN Option "X" ABS (Positive Ground System) (Positive Ground System) 407226786 Lens Cover 406156729 Lamp Socket Option "Y"...
  • Page 46: Figure 3-18: P102 Factory Alarm Wiring

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) Monitored PWB From Frame Alarm LED To Frame Alarm Terminal E3 Figure 3-18: P102 factory alarm wiring 3 - 32 Product Description Issue 4 March 1998...
  • Page 47: Figure 3-19: P101 Frame Power Loss Alarm Wiring

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) Monitored PWB Form-C Alarms During Power Loss in BDFB Figure 3-19: P101 frame power loss alarm wiring Issue 4 March 1998 Product Description 3 - 33...
  • Page 48: Figure 3-20: Fuse Alarm Wiring For Positive Plant P101

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) Monitored PWB Form-C Contacts for Fuse Alarms Figure 3-20: Fuse alarm wiring for positive plant P101 3 - 34 Product Description Issue 4 March 1998...
  • Page 49: Installation

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) Installation Installation • Frame ground mounting hardware (1/4 inch) • Battery and battery return lead mounting hardware (3/8 Material inch) Provided • Load lead mounting hardware (1/4 inch) • Load lead return mounting hardware to internal discharge...
  • Page 50: Cabinet Anchoring

    (4) 3/8 inch drop-in anchors with threaded rod Installing When the BDFB is used in an 11-1/2 foot environment, order either the J85568C-1 List 3 or List 1, J. List 3 includes a 9 foot Extension cabinet, a 2-1/2 foot extension cabinet and interconnection Cabinet for 9 hardware.
  • Page 51: Cable Routing Strategy

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) (4) 804220838 screw, HH .625-11x1-1/2 (4) 840058044 lock washer .625 (4) 814251930 washer .625 Interframe ground cable and mounting hardware is also furnished to provide a continuous frame ground to the top of the cabinet.
  • Page 52: Central Office Ground

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) Table 4-B: Recommended Double Hole Terminal Lugs For Frame Ground KS-5482 Wire KS-20921 Wire WP-91412 List Bolt Size Centers Die Code OMCODE 406021626 0.250 0.62 405347519 0.250 0.62 Blue 405347576 0.250...
  • Page 53: Figure 4-1: Bdfb Floor Footprints (Top, 7-Foot Cabinet, Bottom, 9-Foot Cabinet)

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) 25.94 23.63 19.31 Anchor Bolt Slot .75 x 1.00 Nut 5/8-11 (4 Places) (4 Places) 25.94 23.63 19.31 Anchor Bolt Slot .75 x 1.00 Nut 5/8-11 (4 Places) (4 Places)
  • Page 54: Figure 4-2: H569-407 Group 10 Floor Mounting Detail

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) 841068777 Nut, Hex .375-16 841628639 841068174 Bushing, Insulating Stud 3/8 x .52 Inch or .375-16 x 2-1/2 841630163 Bushing, Insulating 841630155 3/8 x .82 Inch Wsh, Flat .375 841630155 Wsh, Hold Down...
  • Page 55: Figure 4-3: Cable Rack Location

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) Figure 4-3: Cable Rack Location Issue 4 March 1998 Installation 4 - 7...
  • Page 56: Digital Meters

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) Discharge return buses located in the BDFB are also equipped with a C.O. ground termination point. Lists 21-26 provide bus bar assemblies for busing battery to each fuse panel. Discharge return cabling from the battery plant is terminated to these assemblies at the top (or bottom) of the cabinet.
  • Page 57: Figure 4-4: Central Office Ground Terminations

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) A stamping area is provided under each switch position for the installer to stamp load bus designations. The recommeded stamping sequence begins with load bus A for panel position 1 and proceeds through load bus F for panel position 6.
  • Page 58: Alarm Circuit Modules

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) Negative Ground Plant METER TERMINAL Meter Power Shunt Leads - Rtn +130V +24V +48V Pin 11 Pin 12 Batt Batt Batt To Switch Assy To Fuse Panel Terminal Block Positive Ground Plant...
  • Page 59: Alarm Outputs

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) contain installer stamping areas for load designations, and the size and location of the circuit breaker feeding each load bus. See Figure 4-7. Alarm Outputs Each alarm module provides two form-C contacts for power loss and three form-C contacts for fuse failure.
  • Page 60: Frame Alarm Lamp

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) Power Loss Alarm Remote monitoring of power loss is furnished for individual fuse panels. However, power loss alarms will probably not be remotely monitored in most applications because loss of power in a BDFB usually results in a number of other simultaneous alarms from the battery plant and load equipment.
  • Page 61: Alarm Verification

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) to terminal E3. Connect the return lead from the external discharge return bus located on the cable rack to solder terminal E4. For a positive plant (negative ground, reverse these two leads.
  • Page 62: Figure 4-6 Accessing Alarm Modules

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) L u c e n t L IN 2 0 0 Figure 4-6 Accessing Alarm Modules 4 - 14 Installation Issue 4 March 1998...
  • Page 63: Figure 4-7: Load Designation Labels

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) FEEDER BAY: Location ID Breaker/Fuse ID BDFB: Panel Load Voltage Power Fuse Alarm PANEL STATUS Figure 4-7: Load Designation Labels Issue 4 March 1998 Installation 4 - 15...
  • Page 64: Figure 4-8: Alarm Output Connector

    Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) 405095043 DA 15PF179 15 Pos Connector E/W Wire Wrap Pins (Cinch) Figure 4-8: Alarm Output Connector 4 - 16 Installation Issue 4 March 1998...
  • Page 65 Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) Product Warranty A. Seller warrants to Customer only, that: 1. As of the date title to Products passes, Seller will have the right to sell, transfer, and assign such Products and the title conveyed by Seller shall be good;...
  • Page 66 Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) Warranty Period Repaired Product Product Type New Product or Part* Central Office 24 Months 6 Months Power Equipment** The Warranty Period for a repaired Product or part thereof is as listed...
  • Page 67 Lucent Technologies Lineage 2000 ® Battery Distribution Fuse Bay (BDFB) associated with returning such Product to Seller shall be borne by Customer. Seller shall pay the cost of transportation of the repair or replacing Product to the destination designated by Customer within the Territory.