Amana ASXC16 Service And Troubleshooting page 62

Asxc, dsxc, and gsxc condensing units, aszc, dszc, and gszc split system heat pumps with r-410a refrigerant blowers, coils, & accessories
Table of Contents

Advertisement

SERVICING
LED Display
View 6 most recent fault codes and Clear Fault Codes if desired
FCL
(outdoor communicating units)
Menu is enabled if the CFS menu is set to 6. Select the target time
t gt
the system will attempt to satisfy the thermostat.
Menu is enabled if the CFS menu is set to 6. Select the percentage
SUP
past the target time when the system will enable electric heat
operation during heat mode.
Menu is enabled if the CFS is set to 6. (Electric heat will run during
O t t
the next heat call if the heat pump fails to satisfy the custom target
time for this number of consecutive cycles) (default = 20 cycles)
Menu is enabled if the CFS menu is set to 6. (if the addition of low
stage electric heat is able to consecutively satisfy the thermostat
vt t
under the set target time for this number of cycles, the system will
transition to the heat pump for primary heating)
Menu is enabled if the CFS menu is set to 6. (this percentage will
help determine when switching back to heat pump only operation is
SdP
appropriate. Default = 20%. If target time = 20 minutes, the addtion
of low stage electric heat must staisfy the thermostat by less than 16
minutes. (target time - 20% default = 16 minutes).
Menu Description
Air Handler Display (B*)
62