Technical Data - S+S Regeltechnik PHOTASGARD RHKF-UP Operating Instructions, Mounting & Installation

Room light intensity sensors with active output, in-wall, panel switch programme
Table of Contents

Advertisement

Available languages

Available languages

  • ENGLISH, page 6
G
®
PHOTASGARD
The room light intensity sensor PHOTASGARD
intensity and is used to control luminaries, lighting systems, Venetian blinds and
canvas blinds, etc., to monitor lighting conditions at workplaces, in storage halls,
workshops and corridors, in indoor areas, in industrial halls, in offices as well as in
residential and business facilities, for daylight-dependant constant light control,
as light intensity or twilight sensor and to control sunshade equipment avoiding
unnecessary heating-up of rooms. The sensor used in PHOTASGARD
sensors was specifically adapted to the sensitivity of the human eye. Its greatest
sensitivity is in the range of 350 nm to 820 nm. Therefore with its special filter the
sensor is predestined for exposure measurement of daylight and ⁄ or for measuring
artificial light of high colour temperature (similar to sunlight).

TECHNICAL DATA:

Power supply: ........................ 24 V AC ⁄ DC,
Power consumption: ................ < 1 VA at 24 V DC
Sensor:................................. photodiode
Measuring ranges: .................. 1 kLux or 20 kLux,
Output: ................................. 0 -10 V (linearised)
Ambient temperature: ............. 0...+ 50 °C
Measuring error: .................... < ± 10 % of final value
Temperature drift: .................. < ± 5 % of final value ⁄ 10 K
Enclosure: ............................. plastic
Mounting: .............................. in in-wall flush box Ø 55 mm, in-wall
Electrical connection: .............. 0.14 - 2.5 mm²,
Protection class: .................... III (according to EN 60 730)
Protection type: ..................... IP 20 (according to EN 60 529)
Standards: ............................ CE conformity, electromagnetic compatibility
SWITCH PROGRAMME:
Manufacturer: .......................... Busch-Jaeger Reflex Si
Enclosure: ............................. plastic, standard colour alpine white
Type ⁄ WG1
RHKF - UP
R H K F - U P 1 U
R H K F - U P 2 0 U
R H K F - U P 1 S
R H K F - U P 2 0 S
Extra charge:
RHKF - UP
®
RHKF-UP measures the luminous
current consumption max. 10 mA at 24 V DC
(Other individual measuring ranges optional,
e. g. 100 kLux)
or potential-free normally open contact 24 V,
with adjustable switching threshold
via plug terminals on circuit board
according to EN 61 326 + A1 + A2,
EMC directive 2004 ⁄ 108 ⁄ EC
(other switch programmes, manufacturers,
colours and prices upon request)
(similar RAL 9010)
(other colours are possible on request
with colour variants depending on the respective
light switch programme)
Measuring Range
Light Intensity
0 ...1 kLux
0 ... 20 kLux
0 ...1 kLux
0 ... 20 kLux
Other individual measuring ranges optional, e. g. 100 kLux
Schematic diagram
®
light intensity
GND-terminals (1) and (3)
are connected on the circuit board.
Schematic diagram
GND-terminals (1) and (3)
are connected on the circuit board.
Output
Light Intensity
0 -10 V (linearised)
0 -10 V (linearised)
0 -10 V (linearised) ⁄ Normally open contact
0 -10 V (linearised) ⁄ Normally open contact
RHKF - UP - S
GND
Output
Light intensity
0-10V
UB -
UB +
GND
2
2
1
1
RHKF - UP - S
5
5
6
6
Normally open
contact 1
contact 2
(exeeding limit value)
GND
0-10V
UB -
GND
UB +
2
2
1
1
Item No.
1 601-511 1-3000-00 0
1 601-511 1-4000-00 0
1601-51 11-3100 -0 00
1601-51 11-4100 -0 00
3
3
4
4
3
3
4
4