AC500 System data and system construction
The product family Advant Controller 500 control system is designed according to EN 61131-2 IEC
61131-2 standards. Data, different from IEC 61131, are caused by the higher requirements of Maritime
Services.

System data

Operating and ambient conditions

Voltages, according to EN 61131-2
24 V DC
process and supply
voltage
absolute limits
ripple
protection against
reverse polarity
120 V AC
line voltage
frequency
230 V AC
line voltage
frequency
120-240 V AC
wide-range supply
line voltage
frequency
Allowed interruptions of power supply, according to EN 61131-2
DC supply
AC supply
Important: Exceeding the maximum power supply voltage (>30 V DC) for process or supply
voltages could lead to unrecoverable damage of the system. The system could be destroyed.
Temperature
operating
storage
transport
Temperature of the Lithium battery
operating
storage
transport
Humidity
Air pressure
operating
storage
____________________________________________________________________________________________________________
V2
AC500 Hardware
24 V DC (-15 %, +20 % without ripple)
19.2 V...30 V inclusive ripple (see remarks above)
< 5 %
10 s
120 V AC (-15 %, +10 %)
47 Hz..62.4 Hz / 50...60 Hz (-6 %, +4 %)
230 V AC (-15 %, +10 %)
47 Hz..62.4 Hz / 50...60 Hz (-6 %, +4 %)
102 V...264 V / 120 V...240 V (-15 %, +10 %)
47 Hz..62.4 Hz / 50...60 Hz (-6 %, +4 %)
interruption < 10 ms,
time between 2 interruptions > 1 s, PS2
Interruption < 0.5 periods,
time between 2 interruptions > 1 s
0 °C...+60 °C (horizontal mounting of modules)
0 °C...+40 °C (vertical mounting of modules and output
load reduced to 50 % per group)
-25 °C...+75 °C
-25 °C...+75 °C
0 °C...+60 °C
-20 °C...+60 °C
-20 °C...+60 °C
max. 95 %, without condensation
> 800 hPa / < 2000 m
> 660 hPa / < 3500 m
1-4
System data
AC500 / Issued: 05.2007

Advertisement