PEERLESS PureFire PFC-625 Installation, Operation & Maintenance Manual page 60

Table of Contents

Advertisement

TROUBLESHOOTING
11. Gas valve closes, Fan returns to ignition speed.
12. 10 second post purge period.
WARNING
When servicing or replacing any components of this
boiler be certain that:
• The gas is off.
• All electrical power is disconnected.
DANGER
When servicing or replacing components that are in
direct contact with the boiler water, be certain that:
• There is no pressure in the boiler. (Pull the release
on the relief valve. Do not depend on the pressure
gauge reading).
• The boiler water is not hot.
• The electrical power is off.
Table 10.1: Lockout Errors
Error
Error Display
Number
0
E2PROM_READ_ERROR
1
IGNIT_ERROR
2
GV_RELAY_ERROR
3
SAFETY_RELAY_ERROR
4
BLOCKING_TOO_LONG
5
FAN_ERROR_NOT_RUNNING
6
FAN_ERROR_TOO_SLOW
58
13. Pump remain energized for pump post purge period.
14. Full unit standby
Do not use this appliance if any part has been under
water. Improper or dangerous operation may result.
Contact a qualified service technician immediately to
inspect the boiler and to repair or replace any part of
the boiler which has been under water.
If overheating occurs or the gas supply fails to shut
off, do not turn off electrical power to the circulating
pump. This may aggravate the problem and increase
the likelihood of boiler damage. Instead, shut off the
gas supply to the boiler at the gas service valve.
Label all wires prior to disconnection when servicing
controls. Wiring errors may cause improper and
dangerous operation. Verify proper operation after
servicing.
Internal Software error. Replace control.
ONE unsuccessful ignition attempt.
– Check for spark by ear. Check for correct spacing on ignition & flame sensor as described
in Section 10.E.5.b.
– Remove flame sensor and check for white build-up. Clean sensor, re-install and attempt
ignition. If ignition still fails perform other actions listed here, replace sensor.
• If sensor appears cracked or bent, replace sensor.
– Confirm fuel pressure at the valve inlet when the valve is open. Low gas pressure can
cause ignition failures. High gas pressure can cause the valve to not operate and/or
damage the valve.
Failure detected in the Gas Valve Relay. Replace Control
Failure detected in the safety relay. Replace Control.
Blocking error present for more than 20 hours.
– Go to last blocking error code. Correct cause.
Fan is not running for more than 60 secs.
– Check fan condition by disconnecting the 5 pin control plug on the blower. Fan should
ramp to full power when the unit is turned on.
– If fan does not power on, check for 120 volts across the brown and blue wires in the three
pin connector. If voltage is present, replace blower.
– If fan powers on check for continuity through blower control harness, 5 pin connector to
J4 connector on control board. If continuity is found replace control. If no continuity is
found, replace harness.
Fan runs too slow for more than 60 seconds
– Check voltage to the blower. A low voltage can cause the blower to run at the incorrect
speed due to lack of power. Replace blower if voltage is correct.
– Check for continuity through blower control harness, 5 pin connector to J4 connector on
control board. If continuity is not found, replace harness.
– Replace control if other actions do not correct issue.
WARNING
CAUTION
CAUTION
Corrective Action