Installation Instructions
ELEKTROMAT
FS 15.20-25,00
Model: 10003485 00002
Pos: null /BA_Module/BA_Seitenumbruch @ 0\mod_1190719383361_0.docx @ 550 @ @ 1
-en-
Status: 27.05.2021

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ELEKTROMAT FS 15.20-25,00 and is the answer not in the manual?

Questions and answers

Summary of Contents for GFA ELEKTROMAT FS 15.20-25,00

  • Page 1 Pos: null /BA_Module/BA_AA Deckblatt/BAAA000001_M003 @ 17\mod_1444211755814_28.docx @ 891110 @ @ 1 Installation Instructions ELEKTROMAT FS 15.20-25,00 Model: 10003485 00002 -en- Status: 27.05.2021 Pos: null /BA_Module/BA_Seitenumbruch @ 0\mod_1190719383361_0.docx @ 550 @ @ 1...
  • Page 2: Table Of Contents

    Pos: null /BA_Module/BA_DA Inhaltsverzeichnis/BADA000002_M001 @ 5\mod_1342530432542_28.docx @ 754855 @ @ 1 Table of contents Safety-relevant chapter ..........................3     Explanation of symbols ........................... 3   Specified use ..............................3   Target audience of the installation instructions ....................3   General safety instructions ..........................
  • Page 3: Safety-Relevant Chapter

    Observe all specifications, especially warnings, when installing the product in the overall system. GfA is not liable for damage resulting from non-observance of the installation instructions. The resulting overall system must be reassessed for its safety in accordance with applicable standards and directives (e.g. CE marking).
  • Page 4: General Safety Instructions

     Disconnect all cables from the power supply.  Observe valid regulations and standards.  Use suitable tools. Pos: null /FS_ELEKTROMATEN_Module/Sicherheitskapitel_FS_Adresse-GfA @ 66\mod_1618401305511_28.docx @ 1747514 @ @ 1 Pos: null /BA_Module_Manuell/Allgemeine_Module/BA_Seitenumbruch @ 29\mod_1567592807787_0.docx @ 1515778 @ @ 1 GfA ELEKTROMATEN GmbH & Co. KG Wiesenstraße 81...
  • Page 5: Technical Data

    Pos: null /FS_ELEKTROMATEN_Module/Technische Daten/Module/TD_00_Abtriebsdrehzahl @ 32\mod_1581323779969_28.docx @ 1578026 @ 1 @ 1 2 Technical data Designation Unit Output speed Pos: null /FS_ELEKTROMATEN_Module/Technische Daten/Module/TD_01_Allgemeine_Technische Daten @ 62\mod_1604419390202_28.docx @ 1712036 @ @ 1 Output torque 150 (-) Output / hollow shaft 25,00 Series FS 15 Limit switch range...
  • Page 6: Product Overview

    Pos: null /FS_ELEKTROMATEN_Module/Produktübersicht/Produktübersicht_FS_Komponenten_C @ 33\mod_1587034546368_28.docx @ 1646141 @ 1 @ 1 3 Product overview Designation Output shaft: Note the recommendation for the number of teeth on the sprocket and the pitch in the technical data. Spur gear Intermediate flange with centrifugal brake: In the case of fire, the centrifugal brake regulates the speed that the door uses to close.
  • Page 7: Storing

    Pos: null /FS_ELEKTROMATEN_Module/Lagern/Lagern _ELEKTROMATEN @ 60\mod_1597916702984_28.docx @ 1698026 @ 1 @ 1 4 Storing Store the product in the original packaging. Ensure the following environmental conditions for storage:  Closed, dry, dark and vibration-free rooms  Temperatures between +5 °C and +40 °C ...
  • Page 8: Mechanical Installation

    Pos: null /FS_ELEKTROMATEN_Module/Mechanische Montage/Allgemeine Sicherheitshinweise/FS_MechMontage_allgSicherheitshinweise @ 60\mod_1598341728650_28.docx @ 1698954 @ 12 @ 1 6 Mechanical installation General safety information WARNING Danger to life from electric shock! Working on the mechanics may damage electrical lines or components. Danger to life or risk of severe injury from electric current.
  • Page 9: Mounting

    Pos: null /FS_ELEKTROMATEN_Module/Mechanische Montage/Befestigung/FS_MechMontage_Befestigung_BEF8_AGTFS015 @ 60\mod_1598358709306_28.docx @ 1699244 @ 2 @ 1 Mounting Only use the fastening points shown for mounting the product. Alternative mounting options for separately available accessories are not described here. Use the mounting instructions of the accessories for this purpose. Pos: null /BA_Module_Manuell/Allgemeine_Module/BA_Seitenumbruch @ 29\mod_1567592807787_0.docx @ 1515778 @ @ 1...
  • Page 10: Connection Elements

    Pos: null /FS_ELEKTROMATEN_Module/Mechanische Montage/Verbindungselemente/FS_MechMontage_Verbindungselemente @ 60\mod_1598356251599_28.docx @ 1699116 @ 2 @ 1 Connection elements WARNING Danger to life from falling parts and uncontrolled movements. The permissible loads on structures, walls, fastenings, connection and transmission elements must not be exceeded, even with maximum holding or locking torques. Please note the technical data of the drive unit.
  • Page 11: Work Steps

    Work steps WARNING Danger to life from incorrectly installed transmission elements A chain with too little or too much tension may skip or break. As a result, parts of the door structure may become loose and drop. The drive unit or door construction may also suffer damage. ...
  • Page 12  Tighten the fastening screw of the sprocket.  Tension the chain. The slack side (Ⓐ) must not exceed the height of a chain link (Ⓑ).  We recommend using a chain tensioner.  From an angle of 60°, a chain tensioner is required in the slack side.
  • Page 13: Electrical Installation

    Pos: null /FS_ELEKTROMATEN_Module/Elektrische Montage durchführen/Allgemeine Sicherheitshinweise/ELEK-Montage_ELEKTROMATEN-FS_AllgSicherheitshinweise @ 60\mod_1597921777837_28.docx @ 1698708 @ 12 @ 1 7 Electrical installation General information WARNING Danger to life from electric shock! Improper wiring may result in severe or fatal injury from electrical current.  Allow only competent people to carry out the work. ...
  • Page 14: Attaching The Connection Cables

    Pos: null /FS_ELEKTROMATEN_Module/Elektrische Montage durchführen/Verbindungsleitungen anschließen/FS_ElekMontage_Verbinden_Motorstecker @ 60\mod_1598362352275_28.docx @ 1699344 @ 2 @ 1 Attaching the connection cables  Remove the limit switch cover.  Plug in the motor connector. Pos: null /FS_ELEKTROMATEN_Module/Elektrische Montage durchführen/Verbindungsleitungen anschließen/FS_ElekMontage_Verbinden_Endschalterstecker_NES @ 60\mod_1599822703326_28.docx @ 1701678 @ @ 1 ...
  • Page 15: Mechanical Limit Switch - Function

    If the movement direction of the drive unit does not correspond to the movement command, you can change the rotating direction. If you use a GfA door control, change the output rotating direction by using the programming. Follow the instructions for the door control. Otherwise change the output rotating direction as explained below.
  • Page 16  Disconnect all cables from the power supply.  Swap L1 and L2 in the supply line.  Then switch the voltage back on. Setting the final limit position OPEN  Remove the limit switch cover of the drive unit. ...
  • Page 17  The final limit position OPEN can be corrected by fine adjustment.  Check the door position after a correction. Checking and correcting the emergency limit switch OPEN Setting S3 will automatically preset the emergency limit switch S1. Check whether the preset distance is sufficient.
  • Page 18: Motor Connection

    Pos: null /BA_Module/BA_MA Motoranschluss/Umstrukturierung/BAMA010005_M002 @ 34\mod_1589878882361_28.docx @ 1651202 @ 1 @ 1 8 Motor connection Motor X13 Motor plug X14 Brake plug Magnetic brake Pos: null /BA_Module/BA_NA Endschalteranschluss/Umstrukturierung/BANA001002_M002 @ 54\mod_1593499424091_28.docx @ 1680136 @ 1 @ 1 9 Limit switch connection Thermal contact X12 Limit switch board Emergency OPEN limit switch...
  • Page 19: Working Current Brake

    Pos: null /FS_ELEKTROMATEN_Module/Bremsen/Arbeitsstrombremse/FS_ElekMontage_Arbeitsstrombremse @ 60\mod_1599571861815_28.docx @ 1700955 @ 1 @ 1 10 Working current brake The fire protection drive unit includes a working current brake. The braking force is applied when current is present. When the power supply is interrupted, the door closes by gravity. Pos: null /BA_Module_Manuell/Allgemeine_Module/BA_Seitenumbruch @ 29\mod_1567592807787_0.docx @ 1515778 @ @ 1...
  • Page 20: Maintenance

    Pos: null /BA_Module/BA_WA Abschluss Inbetriebnahme/ Wartung/BAWA000126_M001 @ 62\mod_1604653107963_28.docx @ 1712685 @ 122 @ 1 11 Maintenance WARNING Danger to life from electric shock Improper wiring may result in severe or fatal injury from electrical current.  Allow only competent people to carry out the work. ...
  • Page 21: Checklist For Fault Correction

    In the case of a fault, follow the instructions shown on the door control. Find damage to the door mechanism or door leaf first. The following only mentions faults on the drive unit. When contacting GfA Service, have the serial number of the drive unit ready (see the 11-digit number next to "ID"...
  • Page 22: Disposal

    Dispose of old devices properly according to local legal regulations. Return old devices to the return and collection systems available. You can also return GfA products free of charge. Please apply enough postage to the package and mark it as "old devices".
  • Page 23: Declaration Of Incorporation / Declaration Of Conformity

    RoHS Directive 2011/65/EU The following requirements from Appendix I of   GfA ELEKTROMATEN GmbH & Co. KG the Machinery Directive 2006/42/EC are met: declare under our sole responsibility that the 1.1.2, 1.1.3, 1.1.5, 1.2.2, 1.2.3, 1.2.6, 1.3.2, following product complies with the above 1.3.3, 1.3.9, 1.5.1, 1.5.2, 1.5.4, 1.5.6, 1.5.7,...