We wish to express our thanks for the confidence
in us which you have demonstrated by your interest in
our purchase of the DIESEL-CONTROL 100.
For us, this confidence inspires us to work harder
every day to deserve it, and thus, to justify the tradition
of quality which our products have.
This manual will allow you to see the capacity of
the unit as well as its installation and use.
However, if any doubts should remain, let us know
and we will happy attend to them.
INSTRUCTION
MANUAL
INDICE
THEME
1. FUNCIONAL DESCRIPTION
This is an electronic unit for the automatic
Page
starting and stopping of diesel and petrol engines,
1
with breakdown detection.
3
3
STARTING
3
Starting can be carried out:
3
a) By means of a programmable clock which
3
can be built into the unit.
4
b) By signals from external elements (level
4
sensors, another programmer, etc.).
5
c) Manually ( "MANUAL START" button).
5
The activation time of the starter motor can be
5
adjusted between 1 and 12 seconds ("START"
button).
6
In case of a failure in the starting, the unit will
6
make up to 4 attempts, with 2 minute pauses between
6
them. If all attempts fail, there is an illuminated
7
indicator which warns of the occurrence ("START
FAIL").
The unit will detect the starter failure by means
of the oil pressure.
There is a illuminated warning light for engine
working order ("WORKING").
STARTER FUNCTIONING THEORY
On receiving a start order, be it from the builtin
clock, the manual start or external elements, the unit
activates the starter relay for the prefixed time set by
the corresponding adjustment. On finishing, it waits
for 1 and a half minutes to detect the working of the
engine through the oil pressure.
If it has failed to start, it will carry out up to 4
attempts, separated by a fixed timing of two minutes.
If all these attempts fail to start the engine, the
"START FAIL" indicator will be activated
The contact relay and the "WORKING" indicator
remain activated from start to stop.
If the engine is working and the pressure gauge
input is disconnected, the unit not obey start orders.
There is a CONTACT outlet which remains
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the diesel controll 100 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Progres diesel controll 100

  • Page 1: Table Of Contents

    INSTRUCTION MANUAL INDICE 1. FUNCIONAL DESCRIPTION This is an electronic unit for the automatic Sec. THEME Page starting and stopping of diesel and petrol engines, FUNCIONAL DESCRIPCION with breakdown detection. TECHNICAL CARACTHERISTICS INSTALLATION STARTING 3.1. Wall mounting Starting can be carried out: 3.2.
  • Page 2 activated from when the first attempt at starting is STOP FUNCTION THEORY made until the stop. The stop is carried out by the activation of an An electrovalve for irrigation can also be outlet, for a short period of time, which can be connected to the contact outlet.
  • Page 3: Technical Caractheristics

    2. TECHNICAL CHARACTERISTICS PROGRAMATION Adapt the gantries of programming moving PROTECTION them out (for the time that you want the engine to be Protection against polarity changes in the feed active) or pressing to put them in. input. Protection against power surges. SETTING IN TIME Protection against the chance activation of the Use the command “F”...
  • Page 4: Activation By External Order

    normally be because of the oil pressure gauge, given There are engines which need to work with that if it fails to receive a signal from this gauge, the double injection by way of a small electro-magnet unit will understand that the engine is already working. which will be connected in parallel with the starter.
  • Page 5: Supplementary Relays

    CONNECTIONS SCHEME CONNECTIONS SCHEME 3.6. SUPLEMENTARY RELAYS The supplementary relays on the start and stop outlets will protect the Diesel-control from possible anomalies from problems arising from the high power which the distributor or electro-magnet needs for its correct working. The relays used will be 12v, with a shorting capacity of 20 or 30ª.
  • Page 6: Option Start-Up Of Electric Generator For Net Failure Detection

    The oil pressure gauge is defective or does 3.9. OPTION START-UP OF ELECTRIC GENE- not indicate mass with the engine stopped. RATOR FOR NET FAILURE DETECTION SYMPTOM: The unit is not activated by the clock or external sensor, but is activated by the “MANUAL” button. CAUSES: An internal track is fused.
  • Page 7: Connection Scheme Of

    5. CONNECTION SCHEME OF MISCELLANEOUS OPTIONS ♦ Delay option in the pump input. ♦ Option of 2 irrigation sector with delay in the input pump.
  • Page 8 Option of irrigation plus fertiliser with delay in the input pump.