Specifications
Table 1-4. Specifications
(continued)
Property
Digital outputs
Off output voltage
On output voltage
Off output current
On output current
Analog inputs
Termination unit configured:
Input impedance
Common mode voltage
IMCIS22
Normal mode rejection
Common mode rejection
Response time per channel
(100% step change)
IMQRS22
Normal mode rejection
Common mode rejection
Response time per
channel
(100% step change)
A/D resolution
Analog outputs
Output load - current load
Output load - voltage load
D/A resolution
Current limiting
Short circuit protection
Analog accuracy
Input at 25°C (77°F)
standard condition
Terminal based linearity
Repeatability
Deadband
Accuracy
1 - 6
Characteristic/Value
4, open collector, optically isolated
V
(nominal 24 ±10% VDC or 48 ±10% VDC)
I/O
1.5 VDC maximum
10
µ
A maximum
250 mA maximum at 24 VDC; 125 mA maximum at 48 VDC
4, 1-5 VDC (differential/single ended) or 4-20 mA
1 powered or unpowered current (4-20 mA)
Single ended or differential voltage (1-5 VDC)
>1 MΩ
±10 VDC
>76 db at 50/60 Hz
90 db from DC to 60 Hz
2.4 sec to 95% of final value
37 db at 50/60 Hz
53 db from DC to 60 Hz
0.27 sec to 95% of final value
12 bits for analog inputs
2, 4-20 mA or 1-5 VDC
600 Ω/600 mH (maximum)
>1 kΩ
10 bits for analog outputs
50 mA (nominal)
±0.03% of full scale range
±0.03% of full scale range
±0.03% of full scale range
±0.1% of full scale range
WBPEEUI240769B0