5.3 START-UP

1. Enable the 230 V power supply.
All of the LEDs will light up for 3 seconds.
2. Wait until the status LED displays link mode.
If the device shows another indication, the device is already linked. See 6.2 on how to link the device again.
3. Make sure that the fan box is in link mode.
4. Tap the button. The device tries to link to the control device.
It displays the result in the LED status.
When the communication fails, make sure that the control device is in link mode and try again.

6 CONFIGURATION

Configuration
LOW SPEED
MEDIUM SPEED
HIGH SPEED
CO
SETPOINT
2
LINKING
Blue/red
Blue/green
Red/green/blue
VALUE
Blue (flashing)
Red/green

6.1 CONFIGURING SETTINGS

From the status screen (see 4.1):
1. Tap the button. The mode LEDs show the following selection.
2. If necessary, tap the button within 2 seconds, until the selection shows the element to be configured.
3. Keep the button pressed until the status LED starts flashing white.
4. Release the button. The status LED shows the selected element, and the LED flashing modes show its current value.
5. If necessary, tap the button within 10 seconds, until the mode LEDs show the value to be set.
NOTE
When configuring the fan speeds, make sure that the average fan speed is between the low fan speed and the
high fan speed.
6. Wait 10 seconds and the device will apply the configured value. The LED status and the LED modes show the system
status.
LED STATUS
OFF
Low speed
Off
Medium speed
30%
High speed
60%
CO
setpoint
700 ppm
2
Linking
DAITSU WIRELESS CO
PROBE
2
LED MODES
·
·
·
10%
20%
40%
50%
70%
80%
800 ppm
900 ppm
RHR-SCO2
·
·
30%
40%
60%
70%
90%
100%
1000 ppm 1100 ppm
I 9