M-system R6N-RS2 Instruction Manual page 4

Rtd input module, 2 points

Advertisement

PC CONFIGURATOR
With configurator software, settings shown below are available.
Refer to the software manual of R6CON for detailed operation.
■ CHANNEL INDIVIDUAL SETTING
PARAMETER
Sensor type
Lower range value
Upper range value
Fine zero adjustment
Fine gain adjustment
Scaled range Zero
Scaled range Span
Burnout
■ CHANNEL BATCH SETTING
PARAMETER
Loss of internal bus commu-
nication detection time
Conversion rate
Temperature unit
Limit
AVAILABLE RANGE
Pt 100 (JIS '97, IEC)
Pt 100 (JIS '89)
JPt 100 (JIS '89)
Pt 50Ω (JIS '81)
Ni 100
Cu 10 @ 25°C
Cu 50
Depends on sensor type
Depends on sensor type
-320.00 to +320.00 (%)
-3.2000 to +3.2000
-32000 to +32000
-32000 to +32000
Upscale, Downscale
AVAILABLE RANGE
0.0 – 99.9 (sec.)
250, 500 (msec.)
degC, degF, K
-15 to +115%
Scaled range Zero / Span
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
DEFAULT SETTING
Pt 100 (JIS '97, IEC)
0.00 (degC)
0.00 (degC)
0.00 (%)
1.0000
0
10000
Upscale
DEFAULT SETTING
1.0 (sec.)
500 (msec.)
degC
-15 to +115%
R6N-RS2
EM-7781-BK Rev.3 P. 4 / 4