Lennox VEPS075N432K User Manual page 15

Dc inverter multi vrf system user manual
Table of Contents

Advertisement

DC Inverter Multi VRF System
4.2.2 Allowable Length and Height Difference of Connection Pipe
Y type branch joint is adopted to connect indoor and outdoor units. Connecting method is shown in
the figure below.
NOTE: Equivalent length of one Y-type branch is 0.5m.
Fig.5 Allowable Length and Height Difference of Connection Pipe
Piping parameters of VEPS075N432K , VEPS096N432K , VEPS120N432K :
Total length (actual length) of fitting pipe
Length of farthest fitting pipe (m)
From the 1
st
branch to the farthest indoor pipe
Height difference between ODU and
IDU
Height difference between IDUs
Actual length
Equivalent length
ODU at upper side
ODU at lower side
9
Allowable
value
300m
L1+L2+L3+a+b+c+d
120m
150m
40m
50m
40m
15m
Fitting pipe
L1+L2+L3+d
L2+L3+d