Page 1
Installation and Operation Instructions DLP Series Figure 1: DLP Dimensions and Hardware PRECAUTIONS • EMOVE POWER BEFORE WIRING EVER CONNECT OR DISCONNECT WIRING WITH THE POWER APPLIED O NOT ALLOW LIVE WIRES TO TOUCH THE CIRCUIT BOARD • N ISOLATION TRANSFORMER IS RECOMMENDED WHEN POWERING THE DEVICE WITH •...
PITOT TUBE INSTALLATION (Optional Accessory Ordered) Slip the rubber washer over the threaded end of the pitot tube, keeping the washer as close to the threaded end as possible. Fasten the pitot into the threaded insert on the back of the enclosure. Press the rubber washer against the enclosure. Figure 3: Pitot Tube Installation TUBING SETUP WHEN PITOT TUBE IS INSTALLED Units will be shipped with silicone tubing attached to the high and low pressure barb fittings.
Page 3
Duct Mount Panel Mount Figure 5: DLP Mounting WIRING 16 to 26 AWG twisted pair wires or shielded cable is recommended for all sensors. The hinged cover must be opened to connect wires to the unit’s finger push-button terminal blocks. Each DLP unit can be configured to three output signals: 4-20mA, 0-5V or 0- 10V.
Figure 7: Wiring Connections • When using ½” conduit, the strain relief fitting must be removed from the enclosure. • Make sure that any conduit or metal fittings do not come in contact with the circuit board. ZERO FUNCTION The DLP unit should be “ZEROED” before pressure is applied to the unit. The zero button is used to cancel out any offsets caused by installation and sensor drift.
Page 5
• HOOSE DIFFERENTIAL PRESSURE RANGE BASED ON THE EXPECTED DIFFERENTIAL PRESSURE IN YOUR APPLICATION MOVE SWITCHES TO THE CORRECT POSITIONS AND THEN POWER ON THE TRANSMITTER • MAXIMUM PRESSURE ACI Part No. Maximum Pressure (inWC) DLP-001-W DLP-010-W DLP-040-W Unidirectional Mode •...
Page 6
DLP-010-W DLP-040-W Bidirectional Mode • DIP switch SW3 position five set at BI side. • DIP switch SW3 positions one and two are for Pressure Range Selection. Note: In Bidirectional mode, a value of 0 inWC will have an output equal to 50% of the output signal range (12mA, 2.5V, 5V). DLP-001-W DLP-010-W DLP-040-W...
Table 3: Product Specifications WARRANTY SPECIFICATION The DLP Series pressure transmitters are covered by ACI’s Five (5) Year Limited Warranty, which is located in the front of ACI’S SENSORS & TRANSMITTERS CATALOG or can be found on ACI’s web site: www.workaci.com.
This manual is also suitable for:
A/dlp-001-w-u-n-a-0A/dlp-010-w-u-n-a-0A/dlp-040-w-u-n-a-0A/dlp-001-w-u-n-a-3A/dlp-010-w-u-n-a-3A/dlp-040-w-u-n-a-3...