System Configuration – SERVICE LEVEL
The Service could modify the system configuration using the user interfaces (Infrared or wired remote).
System configuration by Infrared Remote
To enter the Unit Configuration mode in the remote, the MODE button must be pressed with the
LOUVER button for 5 continuous seconds while the remote is in Off mode.
The remote will clear its display. The four-digit time icons will display the configuration item and
the Value of that item will be displayed in the temperature display. If the value displayed in the
temperature display is between 100 and 199, the small 1 icon next to the temperature display
icons is used. If the value displayed in the temperature display is between 200 and 299, the small
2 icon next to the temperature display icons is used.
The configurations initially display whatever the previously transmitted value was, if there is no
previous value, the items will display the default value. The remote will initially display the
configuration item "rAdr" for remote address configuration. When first entering Unit Configuration,
only items 1-6 will be available. If while in Unit Configuration the ON and OFF TIMER buttons are
held for 5 continuous seconds, configuration items 1-15 will be available and item 7 is initially
displayed.
Installation level
Remote Control Functions
At least for 5
continuos seconds
+
Service level - first item
shown (#7 in the menu)
65
Press
to skip in the next
ITEM or
to change the
value
Press the louver button
in order to send the
message with the final
choice to the unit.