Operating Method - LG Multi F A2UW14GFA0 Engineering Product Data Book

Heat pump 50hz/r410a
Table of Contents

Advertisement

3. Installation of outdoor unit
3.10.7 PCB Display(14/16/18/21k Model Only)
It is useful to check the cycle data without LGMV.

Operating Method

Whenever you push the Tact Switch, the cycle information will be shown as below.
h After 1page is displayed, subsequently 2page is displayed.
Tact S/W
14/16k
18/21k
-
1 time
-
2 time
1 time
3 time
2 time
4 time
3 time
5 time
4 time
6 time
5 time
7 time
6 time
8 time
7 time
9 time
8 time
10 time
WARNING
When you push the Tact Switch, use the material non-conducting electricity.
69 _ Heat pump
50Hz/R410A
Item
Low Pressure
Hi Pressure
Discharge Temp.
Cond Out Temp.
Suction Temp.
ODU Air Temp.
Current
Voltage
Comp Hz
DC Link Voltage
Display
Example
1page
890kpa
ʻLPʼ
2900kpa
ʻHPʼ
85°C
ʻDSʼ
-10°C
ʻCSʼ
-10°C
ʻSSʼ
-10°C
ʻASʼ
15A
230V
100Hz
230V
ʻdcʼ
TACT-SW1
2page
ʼ 89ʼ
ʻ290ʼ
ʼ 85ʼ
ʻ-10ʼ
ʻ-10ʼ
ʻ-10ʼ
ʻAʼ
ʻ 15ʼ
ʻVʼ
ʻ230ʼ
ʻFʼ
ʻ100ʼ
ʻ230ʼ

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents