Alarm system for oil-water separators
Hide thumbs Also See for NivOil:
Table of Contents

Advertisement

Available languages

Available languages

For sludge probe (DIP3 = OFF)
these functions correspond to 2 signalization modes, i.e.:
test mode, when starting up the system, alarms actuated without delay for a rapid test and
diagnostic of the system probe + cable + alarm unit.
monitoring mode, during normal operation condition, a delay of 15 min applies to avoid false
alarms (due to turbulences for instance).
the test could be completed with the probe outside the separator and totaly immersed in water.
after the auto diagnostic sequence, the control unit recognized the sludge probe and will:
EN
When the test is completed, fit back the probe inside the separator, immersed in water. Fifteen
minutes would be necessary before the detection may be operating (monitoring mode).
msx531-01_B
- alarming when the probe ends are in the air
Or
- when probe ends are inside 1 cm or 2 cm inside sludges (sand, soils etc.)