Bamo NivOil Instruction Manual page 17

Alarm system for oil-water separators
Hide thumbs Also See for NivOil:
Table of Contents

Advertisement

Available languages

Available languages

Cable extension
the maximal length of an extension is 300 m.
use the specific cable reference sk-pVc-2x1, ateX certified.
the easier way to extend the cable accordingly with AtEX rules, is to use the CEt02 cable
coupling (Pic.B), reference nivoil-Jt, suitable to ateX zone 0 category 1.
the device is delivered with 2 WAgO connectors (Pic. C) for fast coupling.
Pic. C
Pic. B
cable cross section: 4 mm
2
as a maximum
Protection: IP 65 (not for a continuous immersion)
the shield must not be connected.
both ends must be pressed to the limit and pressure cable glands well tightened.
3°) connect the sensors to the control unit nivoil in accordance with the obligations due to ex
area, as shown on the drawing.
the measuring loop, as an intrinsic safe circuit, must not be connected to the ground.
connect the control unit to the main power line.
EN
inputs for all types of nivoil sensors
the NivOil control unit
recognizes automatically
the NivOil sensor type
4°) connect back the ribbon cable and close the cabinet.
msx531-01_B
11-05-2010
17