Integrated Fire Protection System
®
1230
Owner's Operation and Maintenance Manual
Self-contained system
FM-0860-0-10J

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 1230 and is the answer not in the manual?

Questions and answers

Summary of Contents for FireFlex 1230

  • Page 1 Integrated Fire Protection System ® 1230 Owner's Operation and Maintenance Manual Self-contained system FM-0860-0-10J...
  • Page 2 Systems Inc assumes no ® liability resulting from any errors or omissions in this manual, or from the use of the information contained herein. 1230 is a registered trademark of F Systems Inc. Systems Inc. reserves the right to make changes to this manual and the data sheets herewith at any time, without prior notification.
  • Page 3: Table Of Contents

    4.4 PFC-4410RC CONTROL BUTTONS ............................ 11 4.5 TIME AND DATE SETTINGS ............................... 12 5. PROGRAMMING & WIRING DIAGRAMS ........................14 ® 5.1 F 1230 PROGRAMMING ............................14 ® 5.2 F 1230 WIRING DIAGRAMS ..........................15 6. CABINET..................................16 7. LIMITED WARRANTY ..............................18 FM-0860-0-10J...
  • Page 4 ® 1230 Page iv Integrated Fire Protection System & M WNER PERATION AINTENANCE ANUAL THIS PAGE IS LEFT BLANK INTENTIONALLY. FM-0860-0-10J...
  • Page 5: General

    NFPA-72 Fire Alarm Systems manufacturer design manuals: NFPA-2001 Clean agent fire extinguishing system • SEVO Design Manual: SE 1230 500 ENG (latest rev.) Before the installation, the contractor installing the unit shall • Potter PFC-4410RC Manual #5403550 (latest rev.) also be familiar with the following documents and standards: Applicable Local &...
  • Page 6: Features

    (C) thereby venting the pressure on top • Manufactured under ISO-9001 quality control procedures of the discharge valve (B) thus allowing the extinguishing agent NOVEC 1230 to be discharged through the piping and 1.6 CONFIGURATION nozzles.
  • Page 7 1230 Page 3 of 18 Integrated Fire Protection System & M WNER PERATION AINTENANCE ANUAL Figure 1.1 - Single NOVEC 1230 cylinder with electric release Field connection to NOVEC 1230 piping 1230 base (shown without enclosure) FM-076Z-0-15C-1 Components: A Cylinder...
  • Page 8 Page 4 of 18 Integrated Fire Protection System & M WNER PERATION AINTENANCE ANUAL Figure 1.2 - Double NOVEC 1230 cylinder with Main / Reserve Field connection to NOVEC 1230 piping 1230 base (shown without enclosure) FM-076Z-0-15C-2 Components: A Main cylinder (Reserve is the right one)
  • Page 9 Page 5 of 18 Integrated Fire Protection System & M WNER PERATION AINTENANCE ANUAL Figure 1.3 - Double NOVEC 1230 cylinder with Master / Slave Field connection to NOVEC 1230 piping Copper tubing 1230 base (shown without enclosure) FM-076Z-0-15C-3 Components:...
  • Page 10: Clean Extinguishing Agent

    Low Observed Adverse 7.5% 2.2 DESCRIPTION Effect Level (LOAEL) Acute Exposure LC50 NOVEC 1230 is a colorless fluid. It is stored as a pressurized 100,000 800,000 (4 hour rate - ppm) liquid and injected into a room, area, or compartment that has...
  • Page 11: Installation, Operation & Maintenance Instructions

    See figure 1.1, 1.2 or 1.3. Cylinder pressure Temperature 413 psi (28.4 bar) 0°F (-17.8°C) ® 1230 cabinet shall be firmly anchored to the floor. 425 psi (29.3 bar) 10°F (-12.2°C) 2. Open door to mechanical section. 438 psi (30.1 bar) 20°F...
  • Page 12: Sequence Of Operation

    "OUTPUT 2" (2 ALARM) activates. If NOVEC 1230 discharge switch option is selected: c) Pre-discharge delay starts (not exceeding 60 sec). e) "ZONE 3" lamp flashes. Note: The abort station will prevent the NOVEC 1230 f) "DETECTION ZONE 3" (RELEASING) message discharge as long as being maintained if activated during appears on the display.
  • Page 13: Emergency Instructions

    ® 1230 Page 9 of 18 Integrated Fire Protection System & M WNER PERATION AINTENANCE ANUAL 3.5 EMERGENCY INSTRUCTIONS 3.7 ELECTRIC ACTUATOR When the electric actuator (C) gets energized, it stays in the To take system out of service: activated position (see figure 3.1).
  • Page 14: Inspections & Tests

    Authority Having Jurisdiction upon request. Typical records include, but are not limited to, detection system, and NOVEC 1230 cylinder inspections. Acceptance test records should be retained for the life of the system.
  • Page 15: Controls

    GROUND FAULT equipment. ZONE circuit active (4) ALARM SILENCE The releasing circuit disabled switch of the NOVEC 1230 is OUTPUT circuit active (4) PRE-DISCHARGE / DISCHARGING located at left of the release control panel. SUPERVISORY 1 / ABORT The control panel can be easily flipped once unlatched from...
  • Page 16: Time And Date Settings

    ® 1230 Page 12 of 18 Integrated Fire Protection System & M WNER PERATION AINTENANCE ANUAL 4.5 TIME AND DATE SETTINGS Figure 4.1 - Cabinet doors assembly The right door is available only with cabinet greater than 24". Time and date settings must be done for each cold start of the control panel.
  • Page 17 ® 1230 Page 13 of 18 Integrated Fire Protection System & M WNER PERATION AINTENANCE ANUAL Figure 4.2 - Control equipment layout Disengage hook for rotation of control panel Junction box TBA, TBB & TBC (behind control panel) CYLINDER MAIN...
  • Page 18: Programming & Wiring Diagrams

    The Potter PFC-4410RC release control panel included with requirements. ® 1230 unit is factory programmed and wired for the following configurations: Note : The control panel motherboard is factory pre-wired ♦ Activation by ZONE 1 OR ZONE 2 (single zone) or and programmed for the configuration selected at the ♦...
  • Page 19 1/4W RELEASING RELEASING Activated by ZONE 3 - Power limited (supervised) initiating device circuits Releasing switch on NOVEC 1230 cylinder SUP 1 / ABORT and SUPERVISORY 2 End of line: 5.1KΩ, ¼W Optional Class A (Style D) Wiring Requires modules Model: CA2Z Leave EOL (provided) on all unused circuits.
  • Page 20: Cabinet

    PERATION AINTENANCE ANUAL 6. CABINET ® 1230 cabinet is made of sturdy 14 gauge Figure 6.1 - Drilling details steel. All surfaces are rust proof coated, inside and outside, with Drilling area fire red, oven baked polyester powder on phosphate base.
  • Page 21 12¾" 77⅛" 46" 46" 25" 50" 15" 48" 23" 54" 54" 31" 81" 58" 21" 56" 26" Table 2 - NOVEC 1230 piping installation 1" 2¾" 6" 3¼" 1¼" 2¾" 6" 3¼" 1½" 2¾" 6" 1¾" 2" 6¾" 6" 4¾"...
  • Page 22: Limited Warranty

    Toll Free: (866) 347-3353 Web site: http://www.fireflex.com ◊ Email: but not limited to, property damages, personal injury, revenue info@fireflex.com loss or lost profits, inconveniences, transportation charges or other damages suffered by anyone.