Wiring Diagram
Remote Controller
Main Indoor unit
Outdoor Unit
Power supply
Wiring Specification
Specification of Wires Between Units and Numbers of Wires.
Outdoor unit - indoor unit
(main unit)
Indoor unit
- indoor unit
(main unit)
(sub unit)
Remote controller wiring
Grounding wire of indoor sub unit
Procure necessary parts and perform all connection work locally.
NOTES
When using the equipment at the first time, it will take a lot of time that the remote controller accepts an operation after power
was on. However, it is not a trouble.
Automatic address
While automatic addressing, the operation can not be performed on the remote controller.
For automatic addressing, Max. 10 minutes (generally, approx. 5 minutes) are required.
When power will be turned on after finish of automatic addressing;
It will require Max. 10 minutes (generally, approx. 3 minutes) that outdoor unit starts operation after power was on.
A
B
1
2
3
3
1
2
L
N
No. of wires
Wire diameter
No. of wires
Wire diameter
No. of wires
Wire diameter
Sub Indoor
A
Unit
1
4 (Include ground wire)
H07RN-F or 245IEC66 1.5 mm
H07RN-F or 245IEC66 1.5 mm
2
Between 0.5 mm
and 2 mm
H07RN-F or 245IEC66 1.5 mm
6
B
2
3
2
or more
2
2
or more
2
2
(up to 200 m)
2
or more