Control Panel - Thiele Tri-One 10000 Manual

Table of Contents

Advertisement

Press "On" on the front panel to start the UPS and in the meantime, the LCD display will light
up. You may view the data and set parameters on the LCD display and the LED display of
the UPS will show the latest status of the UPS. Display will show NOR Cod. 6 message,
Yellow LED will be on and an acoustic signal will be emitted every 2 sec. (Battery will be
discharging).
4.2.2 Turn Off operation
1) Turn off the UPS in line mode:
a)
Press and hold the OFF key for 2 seconds to turn off the inverter and the UPS is in
Bypass mode now; on the contrary, you may press the hold the OFF key for 2 seconds
in order to Change over back to inverter mode
b)
To shut down (turn off) the UPS completely, you need to turn off the input switch.
2) Turn off the UPS with connecting batteries (no mains):
a)
Press and hold the OFF key for 2 seconds to turn off the UPS.
b)
After UPS is turned off, all LED and LCD will be extinguished and there is no output.
Nota: When the UPS is turned off from the inverter mode, it will discharge DC Bus and then shut
down completely; therefore, sometimes, it takes more several seconds to complete.

4.3 Control Panel

4.3.1 LED and control panel display
1
2
3
4
4.3.2 LCD display
NOTE! The display provides more functions than those described in this manual. There are 11
interface available in the LCD display:
ITEM
01
Code
02
Input Phase A
03
Input Phase B
04
Input Phase C
05
Battery +
06
Battery -
07
Output
08
Load
09
Temperature
10
DC Bus Voltage
Software version &
11
model
Ver02 17.11.2014
klick to
klick to
www
www
u-s-v
Y O U R C O N N E C T I O N TO S A F E T Y
ACDC-DCDC
DESCRIPTION
Operational mode and status
Voltage and Frequency
Voltage and Frequency
Voltage and Frequency
Voltage and Current
Voltage and Current
Voltage and Frequency
Load
PFC/Internal temperature and Ambient temperature
± DC Bus Voltage
DSP verson of inverter software version and UPS model
klick to
www
Y O U R C O N N E C T I O N TO S A F E T Y
SYSTEME
).
5
1)
2)
6
3)
4)
5)
7
6)
7)
8)
8
CONTENT DISPLAYED
klick to
www
Y O U R C O N N E C T I O N TO S A F E T Y
Y O U R C O N N E C T I O N TO S A F E T Y
CONTACT
YOUR CONNECTION TO SAFETY
ALARM LED (red)
BYPASS LED
(yellow)
BATTERY LED
(yellow)
INVERTER LED
(green)
Display LCD
ENTER (Scroll button)
OFF button
ON button
klick to
www
Y O U R C O N N E C T I O N TO S A F E T Y
CALLBACK
12

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tri-one 15000Tri-one 20000

Table of Contents