ADCP-92-159 • Issue 1 • 2/2015
3.6

Preparing and Connecting a Pre-Connectorized Cable

This section tells how to prepare and connect a multi-fiber cable. The cable being installed must
conform to the breakout dimensions provided.
Use the following procedure.
1. If the cable is being connectorized:
a.
Refer to
b. Associate these variables to the breakout diagrams given in
Figure 18
2. Determine the correct clamp and grommet combination required to secure the cable to the
panel. For details on the cable clamp itself, refer to
3. Determine the cable entry location. Cables may enter the panel from either top or bottom
and may be clamped to either the left or right side.
CABLE TYPE
IFC Stranded
IFC Ribbon
OSP Ribbon
Cable
'L2' +0.0 IN./-6.0 IN.(+0.0 CM/-15.2 CM)
FANOUT LENGTH
'L3' +0.0 IN./-6.0 IN.
(+0.0 CM/-15.2 CM)
CONNECTORS
Page 16
© 2015, Tyco Electronics Corportation
Table 2
for breakout dimensions for variables L2 to L5.
(IFC Ribbon), or
Figure 19
Table 2. Breakout Dimensions
(NOTE: Dimensions are the same for 1RU and 2RU panels.)
FIGURE
L2
Figure 17
52.0 in
(132.1 cm)
Figure 18
50.75 in
(128.9 cm)
Figure 19
52.75 in
(134 cm)
CLAMP POSITION
'L5' +0.0 IN./-6.0 IN.(+0.0 CM/-15.2 CM)
BREAKOUT LENGTH
MULTIFIBER
SUBUNITS
Figure 17. IFC Stranded Cable Breakout Dimensions
(OSP) for the cable type being installed.
Section 3.4 on Page
L3
L4
25.25
N/A
(64.1 cm)
24.75 in
26 in
(62.9 cm)
(66 cm)
24.75 in
28 in
(62.9 cm)
(71.1 cm)
HEATSHRINK
6.0 IN. (15.2 CM)
(IFC Stranded)
Figure 17
14.
L5
53.25
(135.3 cm)
53.25
(135.3 cm)
54.75 in
(139.1 cm)
OSP/IFC
CABLE
25717-A
CLAMP