IBA ibaBM-SLM Manual

Monitor for siemens simolink bus

Advertisement

Quick Links

ibaBM-SLM
Monitor for Siemens Simolink Bus
Manual
Issue 2.0

Advertisement

Table of Contents
loading

Summary of Contents for IBA ibaBM-SLM

  • Page 1 Monitor for Siemens Simolink Bus Manual Issue 2.0...
  • Page 2 Required corrections are contained in the following regulations or can be downloaded on the Internet. The current version is available for download on our web site http://www.iba-ag.com. Protection note Windows® is a label and registered trademark of the Microsoft Corporation. Other pro- duct and company names mentioned in this manual can be labels or registered trade- marks of the corresponding owners.
  • Page 3: Table Of Contents

    Fiber-Optic Interface to the SIMOLINK Bus (X34, X35)........14 7.11 Interface for loading of the ibaPDA parameters sets........14 ibaBM-SLM functionality on the Simolink Bus..........15 Bus Topology....................15 Simolink Bus Characteristics:................15 Topology example ibaBM-SLM with ibaPDA-V6 ..........16 Issue 2.0...
  • Page 4 Manual ibaBM-SLM Mounting and dismounting................17 Mounting and connecting................17 Dismounting ....................17 Initial operation ....................18 10.1 Basic Steps ..................... 18 10.2 Configuration in ibaPDA.................. 18 10.2.1 Hardware Configuration .................. 18 10.2.2 Reference to simulated parameters (simulation mode) ........23 Working with SIMOLINK signals in ibaPDA..........
  • Page 5: About This Manual

    Manual About this manual This manual describes the construction, use and operation of the device ibaBM-SLM. Target group This manual addresses in particular the qualified professionals who are familiar with handling electrical and electronic modules as well as communication and measurement technology.
  • Page 6: Used Symbols

    Manual ibaBM-SLM Used symbols If safety instructions or other notes are used in this manual, they mean: The non-observance of this safety information may result in an imminent risk of death or severe injury:  By an electric shock!  Due to the improper handling of software products which are coupled to input and...
  • Page 7: Scope Of Delivery

    After unpacking check the completeness and intactness of the delivery. The scope of delivery includes:  Device with 2-pole Phoenix screw terminal  Documentation for the device (iba)  SLB SIMOLINK Board Documentation (Siemens) as well as extended information to this document ...
  • Page 8: Product Description

    Product description Application The ibaBM-SLM device can be used to capture data from one or more frequency con- verters of the SIMOVERT masterdrive series. The SIMOLINK Board (SLB) is integrated in the SIMOVERT Masterdrive in order to guarantee the communication via the SIMOLINK bus.
  • Page 9: Ibabm-Slm

     bit; via ibaPDA packed binary input through bit selection from 16-bit status words Each data type corresponds to a measuring value. Up to 128 analog (INT16; DINT) and 128 packed binary signals per ibaBM-SLM device can be transmitted to ibaPDA. Note Regardless of selected data types, all data are transmitted as 32-bit IEEE floating point values.
  • Page 10: Overview Device Configuration

    - Data storage” menu in ibaPDA-V6. You can define profiles which are avail- able for several data stores and the number and the names of the data stores.  The configuration defined in ibaPDA is transmitted from the ibaPDA computer to ibaBM-SLM via the serial interface. Issue 2.0...
  • Page 11: Device Design

    Device Design Two circuit boards encased in a robust iba metal housing provide the circuitry neces- sary for interfacing with the Siemens Simolink bus. A basic circuit board handles the iba technology and the SLB module handles the Siemens SLB technology.
  • Page 12: Device View, Connections And Displays

    Manual ibaBM-SLM Device view, Connections and Displays 7.3.1 Device views Front view Top view Serial number and support address LEDs for status display (Run, Link, Error) Power supply (24 V DC) (X14) Notebook connection (X30, X31) SIMOLINK LEDs Bottom view...
  • Page 13: Status Display

    LED automatically resets 24 V DC Power Supply (X14) The ibaBM-SLM device is powered by an external, unregulated 24 V DC (20-30 V DC) with approx. 350 mA. Connect the +/-24 V DC terminal from the power supply to the 2- pole Phoenix connector (supplied with device).
  • Page 14: Power Supply Connectors For Simolink Bus (X15)

    SLB SIMOLINK Board Documentation. Important note When a single ibaBM-SLM device is in service, always connect this device at the end of the ring (ibaBM-SLM TX with RX of Busmaster). Should a second ibaBM-SLM de- vice be installed, position the device at the beginning of the ring. This is also necessary when no global messages are to be measured.
  • Page 15: Ibabm-Slm Functionality On The Simolink Bus

    Data received from and transmitted to the SIMOLINK bus is stored in the SLB dual- port-RAM, where it is read by the ibaBM-SLM CPU, converted into floating point format and forwarded to ibaPDA, saved as measuring files and analyzed by ibaAnalyzer.
  • Page 16: Topology Example Ibabm-Slm With Ibapda-V6

     A notebook PC with ibaPDA can be used in parallel.  The ibaPDA computer or the notebook PC must be connected to ibaBM-SLM via a serial cable in order to transmit configuration data before measuring. This connec- tion is not required during measurement.
  • Page 17: Mounting And Dismounting

    SIMOLINK bus topology. Dismounting 1. Disconnect the power supply and all external connections from the ibaBM-SLM de- vice. 2. Grasp the device with one hand firmly on the top side. With your free hand, grasp the bottom of the device so that your index and pointer fingers rest on the ground- ing screw.
  • Page 18: Initial Operation

    1. Mount the ibaBM-SLM device 2. Prepare the ibaPDA computer (insert the ibaFOB card, install ibaPDA-V6 software) 3. Integrate ibaBM-SLM into the SIMOLINK bus (establish the connections) 4. Connect the device to the ibaPDA computer via the serial interface with a V.24 inter- face cable.
  • Page 19 If the device should use the SIMOLINK interrupt, use at least the first link (Link 0). Note SIMOLINK interrupt can only be used, when an ibaBM-SLM device is connected to the 1. link (Link 0), because the card works as interrupt master / external. The SIMOLINK interrupt must be used when measuring synchronously to SLB.
  • Page 20 Manual ibaBM-SLM The SIMOLINK module will be displayed at Link 0 in the module tree on the left side. The “General” tab contains information about the basic settings of the device, the SIMOLINK module and which link is in use.
  • Page 21 Manual To enable/disable the SIMOLINK module as interrupt master, select: False: not enabled True: enabled If you want the SIMOLINK module to give the interrupts to be used, select “True”. 10.2.1.3 COM port configuration Here you should specify:  The COM port, which should be used for loading the parameter set ...
  • Page 22 Manual ibaBM-SLM Proceeding Note The device and ibaPDA must be connected via a serial cable. 1. Click on the “Upload” link. The “Upload” window will be opened. 2. Select the COM port of the ibaPDA computer to which the device is connected via the serial interface.
  • Page 23: Reference To Simulated Parameters (Simulation Mode)

    Manual 3. Then define the conditions, how the device should upload the parameters from ibaPDA or if you want to work with simulated data. Working with simulated data: You can specify, how many simulated parameters (up to 7 are possible) the pa- rameter set should contain.
  • Page 24: Working With Simolink Signals In Ibapda

    The signal table contains all analog signals to be captured from the SIMOLINK bus. Important note Make sure, that the parameter set of SIMOLINK is identical to the parameter set of the ibaBM-SLM device. Assign unique parameters to the signals. These parameters are: Signal name ...
  • Page 25: Technical Data And Environmental Conditions

    350 mA max. FO cable 62,5/125 µm FO coupling ST Lean Distance from ibaBM-SLM to up to 2000 m (6,560 ft) ibaPDA System Dimensions (W x H x D) in mm 54 x 194 x 155 (incl. DIN Rail Clip) inches 2.13 x 7.64 x 6.10...
  • Page 26: Dimension Sheet

    Manual ibaBM-SLM 12.1 Dimension sheet (Dimensions in mm) Issue 2.0...
  • Page 27: Support And Contact

    Koenigswarterstr. 44 90762 Fuerth Germany Phone: +49 911 97282-0 Fax: +49 911 97282-33 Email: iba@iba-ag.com Contact: Mr. Harald Opel Regional and Worldwide For contact data of your regional iba office or representative please refer to our web si- www.iba-ag.com. Issue 2.0...