Cumberland SP-MODULE User Manual

Static pressure module

Advertisement

Quick Links

Static Pressure Module
SP-MODULE
USER'S MANUAL

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SP-MODULE and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Cumberland SP-MODULE

  • Page 1 Static Pressure Module SP-MODULE USER'S MANUAL...
  • Page 2: Table Of Contents

    TABLE OF CONTENTS PRECAUTIONS ............... 3 INSTALLATION ..............4 Description of the SP-MODULE ..........4 Installing the Module on the Wall ..........4 Connecting the Sensor ............7 Connecting the Output Wire ........... 8 USING THE SENSOR ..............9 Description of the SP-MODULE ..........9 TECHNICAL SPECIFICATIONS ..........
  • Page 3: Precautions

    DO NOT SPRAY WATER ON THE MODULE FOR CUSTOMER USE Enter the serial number located on the side of the module below for future reference. Model number: SP-MODULE Serial number: SP-MODULE rev.04...
  • Page 4: Installation

    INSTALLATION DESCRIPTION OF THE SP-MODULE The SP-MODULE is capable of measuring low pressures with a ±1% accuracy - ideally suited for proper building pressurization and air flow control. Transmitters can withstand up to 10 psig overpressure with no damage to the unit. Variable capacitance sensor design provides excellent sensitivity and long-term stability.
  • Page 5 SP-MODULE Fig. 1 Exploded view of the SP-MODULE Do NOT install or use a damaged module. Contact your distributor to obtain another unit. Take a few moments to write the complete serial number found on the side of the module on page 1 of this manual. This will be useful for future reference.
  • Page 6 SP-MODULE Fig. 2 Mounting hole pattern Figure 3 shows how to install the SP-MODULE. The end of the outlet tube must be placed in the ventilated room with the plastic filter pro- vided. This filter prevents insects from entering the tube.
  • Page 7: Connecting The Sensor

    To punch holes through the bottom, use a hammer and punch to carefully punch the holes you need. SP-MODULE rev.04...
  • Page 8: Connecting The Output Wire

    - When extending an output wire, solder all connections. - Never run low voltage cables parallel to high voltage wires to prevent interference. - Output cables must cross power cables at a 90° angle. ALWAYS switch power to the sensor OFF before opening the sensor. SP-MODULE rev.04...
  • Page 9: Using The Sensor

    Whenever possible, any zero and/or span offsets should be corrected by software adjustment in the user's control system. Use the zero and span adjustments on the SP-Module (668 Series) only if abso- lutely necessary. The SP-Module (668 Series) is calibrated in the vertical, position the unit and follow the zero adjustement procedure listed below.
  • Page 10 Span on full scale output adjustments should only be performed by using an accurate pressure standard (electronic manometer, digital pressure gage, etc.) with at least comparable accuracy to the SP-Module (668 Series) (<±1% full scale). With full scale pressure applied to the high pressure port (reference port open to atmosphere) adjust span to achieve 20 mA output.
  • Page 11: Technical Specifications

    Pressure Connection: 3/16" O.D. fitting for 1/4"I.D tubing Minimum Supply Voltage: 12+0.02x(resistance of receiver plus line) Maximum Supply Voltage: 30+0.004x(resistance of receiver plus line) The unit is calibrated at the factory using a 250 ohm load at 28VDC SP-MODULE rev.04...
  • Page 12: Wiring Diagrams

    WIRING DIAGRAMS HIGH MAIN CONTROLLER RECEIVER LOAD RECIVER LOAD SP-MODULE rev.04...
  • Page 13 M 890-00102 rev. 04 REV. 00...