Siemens SIMATIC Manual page 32

Automation system
Hide thumbs Also See for SIMATIC:

Advertisement

3rd Step: Assigning parameters
Step
Action
1
Open your project in SIMATIC Manager.
2
In your project, call the configuration table HW Config.
3
Double-click on the submodule "AI5/AO".
4
Disable analog output 0 per left–click on the "Output
mode" field of the "Output" tab and select "disabled".
Close the dialog with OK.
5
Double-click the "Positioning" submodule.
6
6
Select "Positioning with analog output". In the drive, axis and encoder tabs, customize the
Select "Positioning with analog output". In the drive, axis and encoder tabs, customize the
properties according to your system.
7
Confirm your entries with OK.
8
Save your configuration to your project with
Station > Save and compile.
9
While the CPU is in STOP state, download your confi-
guration via PLC > Load to module....
Close HW Config with Station > Close.
10
6
Result
A split window opens, showing in
the header your project name.
The "Properties AI5/AO2" dialog
opens.
Analog output 0 is enabled for
controlling the motor power unit.
The "Positioning properties" dia-
log opens.
The "Positioning properties" dia-
log closes.
Your changes are now stored in
your project.
Data are downloaded from the
PG to your CPU.
You are returned to SIMATIC Ma-
nager.
Automation System S7-300, Getting Started – Analog
A5E00105537-01