Blower Assembly Removal - Side Access; Figure 8 - Blower Assembly With Captive Panel; Figure 9 - Blower Assembly, Shown Pulled Away From Blower Panel - AAON WH Series Installation Operation & Maintenance

Horizontal water-source heat pump unit
Hide thumbs Also See for WH Series:
Table of Contents

Advertisement

5
Blower Assembly Removal – Side Access
16
1) Using
a
"
shipping screw on the outside of the
right or discharge side of the unit as
shown in the figure below.
2) Remove the side blower access panel
using the panel handle and lift the panel
upwards about ½" or until it clears the
captive panel at the bottom of the blower
panel.
3) Pull the bottom of the blower panel out
about 10 degrees then down and away
from the unit
4) Grip the blower assembly with both
hands and lift it about ½" or until it
clears the captive panel at the assembly.
18
socket,
remove
the
Handle
Figure 8 - Blower Assembly with Captive
Panel
Figure 9 - Blower Assembly, Shown Pulled
Away From Blower Panel
5) Pull the lower half of the blower mount,
away from the blower panel about 10
degrees.