Figure 6 - Drain Trap - AAON WH Series Installation Operation & Maintenance

Horizontal water-source heat pump unit
Hide thumbs Also See for WH Series:
Table of Contents

Advertisement

CAUTION
Unit must not be operated without p-
traps. Failure to install a p-trap may
result in overflow of condensate
water.
Draw-through cooling coils will have a
negative static pressure in the drain pan area.
This will cause an un-trapped drain to back

Figure 6 - Drain Trap

The total height from the trap inlet to the top
of the bottom bend of the trap must be 2"
minimum.
The height from top of the bottom bend of
the trap to the bottom of the leaving pipe
must be at least equal to 1". This ensures
that enough water is stored in the trap to
prevent losing the drain seal during unit
startup.
16
up due to air being pulled up through the
condensate drain piping.
Condensate drain trapping and piping must
conform to all applicable governing codes.
Note: The drain pan connection is an
unthreaded 7/8" stainless steel pipe stub.