Propagation delay or delay skew gives FAIL result
•
Cable is too long (may need to remove coiled service loops)
•
Cable uses different insulation materials on different pairs
Impulse noise is detected
•
Electrical devices near the cabling are generating noise pulses.
•
There is an active link in the same bundle as the cabling under test.
•
Verify that the tester and smart remote are operating correctly. Connect the units together and run an Autotest.
4-8
Table 4-1. Diagnosing Twisted Pair Test Failures (cont.)