NEXT passes, but the plot shows that measurements exceed the limit
For ISO/IEC standards, NEXT is not evaluated where insertion loss is less than 4 dB (the 4 dB rule).
Return passes, but the plot shows that measurements exceed the limit
Return loss is not evaluated where insertion loss is less than 3 dB (the 3 dB rule).
Return loss gives FAIL, FAIL*, or PASS* result
Patch cord or cable impedance not 100 Ω
Patch cord handling causing changes in impedance
Excessive amount of cable jammed into outlet box
Tight service loops in telecommunications closet
Excessive untwisting of pairs at connector
Poor quality connectors
Cable impedance not uniform (poor quality cable)
Table 4-1. Diagnosing Twisted Pair Test Failures (cont.)
Diagnosing Twisted Pair Cabling Faults
Common Causes of Twisted Pair Test Failures
4
-continued-
4-5