Download Print this page

Honeywell PEHA PHC Installation And Operating Instructions page 2

Advertisement

Available languages

Available languages

PEHA Elektro GmbH & Co. KG
Postfach 1727 • D-58467 Lüdenscheid • Tel.: (02351)185-0 • Fax: (02351)27666 • e-mail: peha@peha.de • Internet: www.peha.de
InsTaLLaTIon anD oPeraTInG InsTrucTIons
Phc input modul 940/230 em
8 inputs (230 v alternating current)
940/230 em
DescrIPTIon
The PHC input module 940/230 EM has 8 inputs (I0-I7) for input signals with a
voltage of 230V~/50-60 Hz. At each of the inputs one of the 3 phases (L1-L3) of the
mains power supply can be connected. Please make sure that the neutral wire is
connected to terminal N.
connecTIon DIaGram
N
L
L
L
N
0
1
2
4 x Input
PHC System
8 Inputs 1mA/230V AC
940/230 EM
4 x Input
4
5
6
L
L
L
mounTInG
The installation of the PHC modules may be carried out by authorised technicians only.
During installation the system's electricity has to be switched off. The PHC module is
designed for mounting on a 35mm top hat rail acc. EN 50022 in in-/on-wall distribution
housing. The devices can be mounted directly next to each other. The PHC modules
may not be employed in connection with devices that may endanger people, animals
or property when operated.
The following points must be observed:
Datum
Name
- the valid laws, standards and regulations
Bearb.
23.01.12
Kai Imorde
- the technical state of the art during installation
Kniedruck und Geräteaufkleber
Gepr.
- the PHC manual and the operating instructions of the PHC modules.
Norm
- Operating instructions can only cite general stipulations.
These are to be viewed in the context of a specific system.
The following systems may not be switched by Phc output modules:
Gevener Weg 38 · 58809 Neuenrade
Name
Urspr.: Format DIN A4
Dateiname: GAK 940 230 EM (Rev01_120123)
Ein Betrieb der Unternehmensgruppe
- safety switches such as EMERGENCY OFF
- emergency power supplies
- fire alarm systems
- emergency lighting systems
DaTa connecTIon
The connection between PHC control unit and other PHC modules is established by the
PHC bus line and the modular connectors of the modules. The module connectors are
switched parallel in the modules (except in the PHC power supply unit) and therefore
freely selectable as in- or output. Thus the PHC module can be positioned anywhere
in the data line.
A PHC bus line of 30 cm length is included with every PHC module. It is needed for
connecting a neighbouring module or for connecting a module in the next distributor
row. The modules are supplied with voltage by the bus line. Power needs to be
switched off before disconnecting the bus line.
PEHA_M_940_230_EM (Rev06_130218)
L
Please note!
3
The neutral wire has to be connected
to terminal N.
It makes no difference which phase (L1-
L3) of the mains power supply supplies
the voltage for an input of the 940/230
EM input module.
The inputs are galvanically separated
by optoelectronic couplers from the 24
V module voltage.
coDInG sWITch
module address
7
L
Seite
PHC Input Module 940 230 EM
Gb
coDInG sWITch
The input module's address is set by the coding switch built into the PHC control
module. The setting of the coding switch is presented in the PHC software under the
menu item „Components g Edit Modules".
Make sure that no identical module addresses are given for PHC input modules.
The setting of the coding switch may be carried out by technicians only. For this the
PHC module needs to be switched off and it must be ensured that there can be no
electrical discharge.
currenT consumPTIon
To calculate the current consumption for the power supply, you should assume a
consumption of 10 mA.
TechnIcaL DaTa
Power supply
Phc system (Phc bus)
own consumption
number of inputs
Input voltage
Input current
Input resistance
Input signals
Time for interpreting
an input signal
connection
possibilities
coding
ambient temperature
storage temperature
screw terminals
Test specifications
approbationen
Protection level
Dimensions
WarranTy conDITIons
These operating instructions are an integral part of both the device and our terms of
warranty. They must be handed over to the user. The technical design of the appliance
is subject to change without prior notification. PEHA products are manufactured
and quality-checked with the latest technology according to applicable national and
international regulations. Nevertheless, if a product should exhibit a defect, PEHA
warrants to make remedy as follows (regardless of any claims against the dealer to
which the end user may be entitled as a result of the sales transaction):
In the event of a justified and properly established claim, PEHA shall exercise its
1
prerogative to either repair or replace the defective device. Further claims or liability
for consequential damage are explicitly excluded. A justifiable deficiency is deemed to
exist if the device exhibits a structural, manufacturing, or material defect that makes it
unusable or substantially impairs its utility at the time it is turned over to the end user.
The warranty does not apply to natural wear, improper usage, incorrect connection,
device tampering or the effects of external influences. The warranty period is 24 months
from the date of purchase by the end user from a dealer and ends not later than 36
months after the device's date of manufacture. German law shall be applicable for the
settlement of warranty claims.
DIsPosaL oF The DevIce
Do not dispose of old devices in the household waste! The device must be
disposed of in compliance with the laws and standards of the country in which it
is operated! The device contains electrical components that must be disposed
of as electronics waste. The enclosure is made from recyclable plastic.
126009-05
Nom. 24 V DC
21-28 V DC (ripple voltage 5 %)
10 mA
8 inputs (I0- I7) for 230V input signals
180 - 250V AC
max. 1mA
270 kΩ
> 40ms
The following signals are interpreted:
On > 0 Sec
On > 1 Sec
On > 2 Sec
Off < 1 Sec
Off > 1 Sec
2 modular sockets for PHC bus
8 screw terminals for input signals I0-I7
1 screw terminals for common neutral wire N
DIP switch, 5-pin (Module address)
+10° to +50°C
-20° to +60°C
max. 2 x 1,5 mm²
EN 60669-2-1
CE KEMA/KEUR CEBEC
IP 20
width = 72 mm
height = 55 mm
GB - 1

Advertisement

loading