INSTALLATION AND MAINTENANCE INSTRUCTIONS
302-0004 Twinflex Hipoint

Introduction

The Twinflex Hipoint unit allows for audible indication when the system enters an
alarm condition. This device is compatible with the Twinflex 2-wire range of Fire
Alarm equipment and comprises a 2-wire zone-powered sounder. This device may
be installed on the same zone as the Multipoint detector/sounder and associated
.
Twinflex devices

Before Installation

The Sounder must be installed in compliance with the control panel installation manual. The installation must also
meet the requirements of any local authority. For maximum performance the detector should be installed in
compliance with BS5839 Pt1 : 2002 + A2 : 2008.

Spacing

Fike recommends spacing of sounders in accordance with BS5839 Pt1. For more specific information regarding
sounder spacing, placement and special applications please refer to BS5839 Pt1 : 2002 + A2 : 2008.

Device Installation

Fix the back box in a suitable position using at least two screw holes/slots, remembering to allow enough cable
length for installation. All wiring must be installed in compliance with the recommendations laid out by BS5839 Pt1 :
2002 as well as any special recommendations documented in the control panel installation manual.

Connections

2
The cabling should be 2-core 1.5mm
screened/earthed and fire resistant, of an MICC
or FP200 equivalent type and is to be in the form of a 2-core radial circuit terminating
+
+
at the End of Line device.
No screen connection is allowed for within the device. Incoming and outgoing cable
screens must therefore be connected through using a suitable connector. It is
TO ACTIVATE EOL
MOVE SWITCH 1 TO
important to maintain the screen continuity in order to protect against data corruption
"ON" POSITION
from interference.
4 3 2 1
ON
Once all testing has been carried out on the cabling and continuity & insulation has
been proven, the Hipoint front may be fitted. The Hipoint front is fitted by locating the
rubber seal in the groove on the back box and then pushing the front unit gently
home. The four fixing screws may then be tightened as required.
Remember that the device at the end of the line must have its EOL signal activated using the
relevant DIL switch. Do not use a resistor or capacitor (or another manufacturer's End of Line
device) as the end of line, as this may prevent correct operation of the zone.
CONTROL PANEL
TWINFLEX HIPOINT
TWINFLEX HIPOINT
26-0378 Issue 5

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Twinflex Hipoint and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Fike Twinflex Hipoint

  • Page 1 BS5839 Pt1 : 2002 + A2 : 2008. Spacing Fike recommends spacing of sounders in accordance with BS5839 Pt1. For more specific information regarding sounder spacing, placement and special applications please refer to BS5839 Pt1 : 2002 + A2 : 2008.
  • Page 2 Fike’s policy is one of continual improvement and the right to change a specification at any time without notice is reserved. Whilst every care has been taken to ensure that the contents of this document are correct at time of publication, Fike shall be under no liability whatsoever in respect of such contents.

This manual is also suitable for:

302-0004

Table of Contents