Mounting The Branch Box; Installing Refrigerant Piping - Mitsubishi Electric BRANCH BOX PAC-MKA52BC Installation Manual

Air-conditioners indispensable optional parts
Table of Contents

Advertisement

Available languages

Available languages

6. Mounting the Branch Box

B
C
D ( E )
A
F
G
Fig. 6-1
Bracket
Fig. 6-2

7. Installing refrigerant piping

Flare cutting dimensions
45°± 2°
Table 1
Flare dimensions
Copper pipe O.D.
øA dimensions
ø6.35 (1/4)
8.7-9.1 (11/32-23/64)
ø9.52 (3/8)
12.8-13.2 (1/2-33/64)
ø12.7 (1/2)
16.2-16.6 (41/64-21/32)
ø15.88 (5/8)
19.3-19.7 (49/64-25/32)
Fig. 7-1
B
Flare nut tightening torque
Table 2
Copper pipe O.D.
Flare nut O.D.
(mm (inch))
(mm (inch))
ø6.35 (1/4)
17 (43/64)
ø6.35 (1/4)
22 (7/8)
ø9.52 (3/8)
22 (7/8)
ø9.52 (3/8)
26 (1-3/64)
ø12.7 (1/2)
26 (1-3/64)
ø12.7 (1/2)
29 (1-9/64)
ø15.88 (5/8)
29 (1-9/64)
ø15.88 (5/8)
36 (1-27/64)
Fig. 7-2
(inch)
B
H
* Purchase an appropriate
bracket locally if the unit
is to be mounted on a
wall.
(inch)
(mm (inch))
Tightening torque
(N•m (ft•lbs))
14-18 (10-13)
34-42 (25-30)
34-42 (25-30)
49-61 (35-44)
49-61 (35-44)
68-82 (49-59)
68-82 (49-59)
100-120 (71-87)
(1) Install the suspension bolts (procure locally) at the specified pitch (Fig. 4-2, 4-3).
(2) Fit the washers (1, 2) and nuts (procure locally) to the suspension bolts.
(Fig. 6-1)
(3) Hang the unit on the suspension bolts.
(4) Fully tighten the nuts (check ceiling height).
(5) Use a level to adjust the branch box to the horizontal.
When unit is hung and nuts tightened
A
Suspension bolt
B
Nut (procure locally)
C
Washer (with cushion) 1
D
Ensure that cushion faces downwards
E
Washer (without cushion) 2
F
Nut (procure locally)
G
Ceiling board
H
► Connect the liquid and gas pipes of each indoor unit to the same end
connection numbers as indicated on the indoor unit flare connection
section of each Branch Box. If connected to wrong end connection
numbers, it doesn't work normally.
► When connecting indoor units, make sure to connect refrigerant pipes
and connection wires to the appropriate connection ports marked with
matching alphabets. (Ex. A, B, C, D, E) If connected to wrong end con-
nection numbers, it doesn't work normally.
Note:
Be sure to mark all the local refrigerant piping (liquid pipes, gas pipes, etc.)
for each indoor unit designating clearly which room it belongs in. (Ex. A, B,
C, D, E)
► List indoor unit model names in the name plate of Branch Box (for iden-
tification purposes).
• Conduct sufficient anti-condensation and insulation work to prevent water drip-
ping from the refrigerant piping. (liquid pipe/gas pipe)
• Increase insulation depending on the environment where the refrigerant piping is
installed, or condensation may occur on the surface of the insulation material.
(Insulation material Heat-resistant temperature: 120 °C [248 °F], Thickness:
15 mm [19/32 inch] or more)
* When the refrigerant piping is used in locations subject to high temperature
and humidity such as in the attic, further addition of insulation may be re-
quired.
• Insulate the liquid and gas pipes of the branch box by attaching the heat-resis-
tant polyethylene foam tightly around them. (Fig. 7-4)
Otherwise, a burn during pipe connection work or water leakage due to con-
densation on pipes may result. If connected to wrong end connection numbers,
it doesn't work normally.
► When using commercially available refrigerant piping, ensure that both
liquid and gas piping are wrapped with commercially available thermal
insulation materials (insulation materials at least 1/2 inch (12 mm) thick
and able to withstand temperatures in excess of 100ºC [212°F]).
► Refer to the installation manual of the outdoor unit when creating a
vacuum and opening or closing valves.
7.1. Piping connection procedure
(1) Remove the flared nuts and caps from the branch box.
(2) Flare the end of the liquid and gas pipes as shown in Fig. 7-1.
(3) Apply refrigerant oil on the fl ared seat. (Fig. 7-3)
Use the fl are nut removed from the branch box. Use of an off-the-shelf nut
may lead to a crack in the nut.
(4) Connect the refrigerant piping immediately. Always tighten the flared nuts to
the torque specified in the table 2 using a torque wrench and double spanner.
(Fig. 7-2)
Caution:
Tighten the flare nut with a torque wrench in the specified method.
Overtightening will cause the flare nut to crack and it will cause refrigerant
leakage over a period of time.
en
6

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

Branch box pac-mka32bc

Table of Contents