User unit maintenance checks

General external checks
1. Surfaces
Check for cuts, damage, and debris.
If debris is present, remove it.
If you find damage, contact your supplier.
2. Metalwork
Check for damage and corrosion.
If present, contact your supplier.
3. Interface panel
1. Check the HMI for damage/signs of faded color/pixels that
are clearly visible.
2. Press each button and check if they work.
4. Plug holders
Ensure there is no debris or damage inside or around the plug
holders and plug holder hinges.
If present, remove debris/notify the supplier.
5. Cable Management system
Pull on the cables to check the retraction system of the cables.
If blocked, contact your supplier.
Maintenance Manual
Coolant level and radiator fans check
1. Coolant level inspection
1. Check if the coolant is at the correct level.
Note: The coolant should be above the level indicated by
the arrows in the following image.
2. If the coolant level is below the half-way arrow mark of the
hose, inform the supplier.
2. Radiator fans
1. Periodically check for debris/damage.
2. Clean fins to ensure free airflow.
CAUTION
Clean with water and soft-bristled brushes and/or low-
pressure hoses only to avoid bending or damaging the fins.
Allow to air-dry before operating.