Connecting The Signal Cables - Huawei SUN2000-15KTL-50KTL-M3 Series User Manual

Hide thumbs Also See for SUN2000-15KTL-50KTL-M3 Series:
Table of Contents

Advertisement

Replacing SUN2000-(15KTL-50KTL) Series with
SUN2000-(15KTL-50KTL)-M3 Series
User Manual

6.3.2 Connecting the Signal Cables

COM Port Pin Definitions
Ensure that the protection layers of the cables are inside the connector, that excess core wires
are cut off from the protection layer, that the exposed core wires are totally inserted into the
cable hole, and that the cable is connected securely.
Before Replacement-RJ45
Network Port
No.
Color
Function
1
White
RS485A
and
orange
4
Blue
RS485A
2
Orange
RS485B
5
White
RS485B
and
blue
Issue 01 (2021-04-05)
Before
Replacement-Termina
l Block
No.
Function
1
RS485A IN
2
RS485A OUT
3
RS485B IN
4
RS485B OUT
Copyright © Huawei Technologies Co., Ltd.
6 Electrical Connections
SUN2000-(15KTL-50KTL)-M3 Series
(COM Port)
No.
Definition
Function
1
485A1-1
RS485 differential
signal +
2
485A1-2
RS485 differential
signal +
RS485 differential
3
485B1-1
signal –
4
485B1-2
RS485 differential
signal –
5
PE
Shield layer grounding
6
PE
Shield layer grounding
7
485A2
RS485 differential
signal +
9
485B2
RS485 differential
signal –
Dry contact for power
8
DIN1
grid scheduling
10
DIN2
12
DIN3
14
DIN4
16
GND
63