12 Operation

12.4 Menu list

SP 1 / SP2
Setting the switch on points
FH 1 / FH2
Setting the respective value from which the switch point 1 or 2 should be activated. If the window func-
tion in the menu 5/6 or 5/7 is activated, the value of the switch point is the upper temperature limit of
Menu: 1 and 3
the window (WindowHigh).
rP 1* / rP 2*
Setting the switch-back points
FL 1 / FL2
Setting the respective value from which the switch-back point 1 and 2 should be activated. If the window
function in the menu 5/6 or 5/7 is activated, the value of the switch-back point is the lower temperature
Menu: 2 and 4
limit of the window (WindowLow).
ASt2 / AEn2
If output signal 2 is active (5/17)
Analogue output 2 (change option ± 5% for initial value and 90–100% for end value of the measuring
range), see 13.8 Setting the offset and end value.
* Additional menu
EF
Extended functions
Menu: 5
(Transition to menu level two)
rES
Reset
Restore all adjustable parameters to the as-delivered state and delete the min. and max. values
Menu: 5/1
dS 1 / ds 2
Setting the switch-on delay
Setting the value for the switch-on delay after reaching switch-on point 1 or 2 (adjustable 0.0 to 50.0 s)
Menu: 5/2 and 5/4
dr 1 / dr 2
Setting the switch-off delay
Setting the value for the switch-off delay after reaching switch-off point 1 or 2 (adjustable 0.0 to 50.0 s)
Menu: 5/3 and 5/5
ou1 / ou2
Setting the switching outputs 1 and 2
Switching function of the switching outputs:
Hno = Hysteresis function, make contact
Hnc = Hysteresis function, break contact
Menu: 5/6 and 5/7
Fno = Window function, make contact
Fnc = Window function, break contact
Uni
Switching units
Select the physical unit of measure
for the displayed and set pressure values:
bAr = bar,
Menu: 5/8
nnBa = mbar,
PSi = PSI,
mPA = MPa
FLIP
Rotate display indication by 180°
Menu: 5/9
Lo
Min. value (display only)
Display of the minimum temperature that was present during measurement (the value is lost if the
Menu: 5/10
power supply is interrupted)
Hi
Max. value (display only)
Display of the maximum temperature that was present during measurement (the value is lost if the
Menu: 5/11
power supply is interrupted)
----
Delete the min. and max. values
The display confirms that the values have been deleted
Menu: 5/12
Set0
Zero point adjustment
Setting/correction of the zero point of the display indication and the analogue output signal by up to ±
Menu: 5/13
3% of the measuring range
dAP
Measured value damping
Setting the value for damping (0 to 1000 ms in 10 ms steps)
Menu: 5/14
GEMÜ 3140
First menu level
Second menu level
16 / 24
www.gemu-group.com