1. DESCRIPTION
Viking Model XG Sprinkler Guards and XWU Water Shields are used in conjunction
with Viking XT1 style sprinklers where allowed by the approvals. (Refer to the
Approval Charts) The guards are hard-wire cages designed to encase the
sprinklers and protect them from mechanical damage. They are recommended for
areas where sprinklers are installed at a low elevation and/or near a high degree
of human or mechanical activity.
Water shields protect the sprinkler's heat-sensing operating element from water
spray discharge from sprinklers located at a higher elevation. Viking XT1 style
sprinklers with Model XWU or F-1 Water Shields and/or XG Guards are converted
to intermediate level/rack storage sprinklers. They may be used in any application
where water shielding is required, such as in-rack sprinkler systems, under grating,
on pilot sprinklers for deluge systems, and outdoors as a weather shield.

NOTE:
Sprinkler water shields and guards are not designed to be used on
sprinklers installed in recessed escutcheons.
2. LISTINGS AND APPROVALS
FM Approved: Class 2091
cULus Listed: Category VNIV
XG Guard is approved for use with the following sprinklers:
VK1001, VK1021, VK3001, VK3021, VK2002, VK2022, VK3502, VK3522,
VK2001, VK2021, VK3501, and VK3521
XWU Water Shield is approved for use on XT1 Upright sprinklers with XG Guards:
VK1001, VK3001, VK2002, VK3502, VK2001, and VK3501
F-1 Water Shield is approved for use with XT1 Pendent sprinklers:
VK1021, VK3021, VK2022, VK3521, VK2021, and VK3522
Refer to the Approval Charts for more information.
3. TECHNICAL DATA
Specifications: See Table 2.
Material Standards:
XG Sprinkler Guard: UNS-G10100 Bright Basic Steel Wire or JIS G3141 SPCF
XWU Water Shield: UNS-G10080 Cold Rolled Steel or JIS G3141 SPCF
F-1 Water Shield: UNS-G10080 Cold Rolled Steel
Refer to the approval charts in this document as well as the appropriate sprinkler Technical Data Page.
Part Number
22931
22937
10323
10324
Form No. F_021319
20.10.06
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
TABLE 1: ORDERING INFORMATION AND DIMENSIONS
Guards and water shields must be ordered separately. See below for details.
Model XG Sprinkler Guard
Model XWU Upright Water Shield (must be used with Model XG Guard)
Model F-1 Pendent Water Shield
Model F-1 Pendent Water Shield
Rev 20.2
Description
(Removed pre-assembled options and wrench .)
GUARDS AND WATER
SHIELDS FOR
XT1 SPRINKLERS
XG Sprinkler Guard
XWU Water Shield
F-1 Water Shield
Size
NPT
1/2" or 3/4"
15 mm or 20mm
--
1/2"
3/4"
Replaces Form No. F_021319 Rev 20.1
Page 1 of 8
BSPT
--
15 mm
20mm

Advertisement

loading

Summary of Contents for Viking XG

  • Page 1 VK2001, VK2021, VK3501, and VK3521 F-1 Water Shield XWU Water Shield is approved for use on XT1 Upright sprinklers with XG Guards: VK1001, VK3001, VK2002, VK3502, VK2001, and VK3501 F-1 Water Shield is approved for use with XT1 Pendent sprinklers: VK1021, VK3021, VK2022, VK3521, VK2021, and VK3522 Refer to the Approval Charts for more information.
  • Page 2 XT1 SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com TABLE 2: SPECIFICATIONS Dimensions...
  • Page 3: Installation

    The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com 4. INSTALLATION FIRE HAZARD - RISK OF SERIOUS INJURY OR DEATH DANGER Improper installation can impede the sprinkler operation during fire conditions.
  • Page 4 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com 4. Once the sprinkler is inside the frame and the guard is properly oriented, rotate the guard 90 degrees in either direction so the activation element T-hinge is not blocked.
  • Page 5 1. Install the F-1 Water Shield onto the sprinkler threads as shown below. 2. Install the sprinkler/water shield assembly into the piping according to the sprinkler’s Technical Data sheet. 3. After installing the sprinkler/water shield into the pipe, install the XG guard (if applicable) onto the sprinkler as shown in Section 4A.
  • Page 6: Operation

    Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to the appropriate sprinkler data page. Viking sprinklers are designed to be installed in accordance with the latest edition of Viking technical data, the latest standards of NFPA, FM Global or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards whenever applicable.
  • Page 7 See Table 1 in this document and refer to the appropriate sprinkler technical data page for available temperatures and finishes. For Upright Intermediate Level installation, See NOTE below. NOTE: When Upright XT1 Sprinklers listed on the chart below are equipped with the XG Guard and XWU Water Shield they can be used in intermediate level installation.
  • Page 8: Technical Data

    Footnotes Base part number is shown. For complete part number, refer to Viking’s current price list. Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.