Download Print this page

Viking XG Technical Data Manual page 4

Guards and water shields for xt1 sprinklers

Advertisement

Page 4 of 8
GUARDS AND WATER
TECHNICAL DATA
SHIELDS FOR
XT1 SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
4. Once the sprinkler is inside the frame and the guard is properly oriented, rotate the guard 90 degrees in either direction so
the activation element T-hinge is not blocked. See Figures 4 and 5.
5. Close the guard and tighten the torx screw.
Alternatively, the guard can
be rotated 180° so the T-hinge
pocket on the opposite side is
facing outward.
90°
Activation element
T-hinge facing outward.
Figure 4: Orienting the Sprinkler
Figure 5: Closing the Guard
6. VERIFY THAT THE SPRINKLER IS PROPERLY ORIENTED WITHIN THE GUARD. SEE FIGURE 6 BELOW.
Improper installation will impede
proper sprinkler operation. In this
example, the sprinkler activation
element T-hinge is not facing
outward and is blocked.
Figure 6: Improper Alignment
Form No. F_021319
20.10.06
Rev 20.2

Advertisement

loading

This manual is also suitable for:

XwuF-122931229371032310324