4. INSTALLATION

DANGER
Improper installation can impede the sprinkler operation during fire conditions. Fire can lead to serious injury or death.
► Follow the procedures in this document to properly install the sprinkler guard.
A. Installing the XG Sprinkler Guard on the Sprinkler
Tools needed:
T15 Torx screwdriver (not available from Viking.)
Procedure:
1. Install the sprinkler into the piping according to the sprinkler's Technical Data sheet.
2. Loosen the Torx screw and open the guard.
Figure 2a: Opening the Guard
3. With the sprinkler frame arms parallel to the vertical guard members, maneuver the guard onto the sprinkler.
NOTE:

For Upright sprinklers, the guard must be oriented and angled as shown (Figure 3a) in order to get the
deflector inside the frame.
Figure 3a: Maneuvering the Guard onto the Sprinkler
Form No. F_021319
20.10.06
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
FIRE HAZARD - RISK OF SERIOUS INJURY OR DEATH
Rev 20.2
GUARDS AND WATER
XT1 SPRINKLERS
Figure 2b: Opening the Guard
Figure 3b: Maneuvering the Guard onto the Sprinkler
Page 3 of 8
SHIELDS FOR

Advertisement

loading