ACHIBAei Heat pump PACKAGED AIR-AIR – COMPACT HORIZONTAL INVERTER UNITS Models: 17ei │ 22ei │ 27ei │ 35ei Cooling capacities : from 17 kW to 33.3 kW Heating capacities : from 18.9 kW to 36.9 kW IOM_ACHIBA ei_17ei a 35ei_208024_200104_EN...
Page 2
COMPACT HORIZONTAL INVERTER Thank you for trusting the Hitecsa Products. Our company has been offering the market an extended range of specialized units for air conditioning and cooling installations for over 35 years. Our approach is based on efficiency, flexibility and on practical solutions.
ACHIBAei AIR-AIR PACKAGED UNITS COMPACT HORIZONTAL INVERTER INTRODUCTION Purpose of this Manual This manual and any other instructive document attached as refrigeration lines design, electrical diagrams, etc. have been written to allow a correct installation, commissioning and maintenance of the unit. Therefore it is essential to read the instructions with due attention. Verify that all the necessary information for the correct installation of the system is included in the manuals supplied with this unit and/or the rest of the indoor units, accessories, etc.
ACHIBAei AIR-AIR PACKAGED UNITS COMPACT HORIZONTAL INVERTER INTRODUCTION Periodic Inspections and Maintenance Carry out periodic inspections to detect possible damaged or broken parts. If these parts are not repaired it could cause damage to people or material. Before executing any maintenance operation, switch the unit power supply off.
ACHIBAei AIR-AIR PACKAGED UNITS COMPACT HORIZONTAL INVERTER SAFETY PRECAUTIONS WARNING! Before starting any installation, service or maintenance operation, turn the main power switch off in order to avoid electrical shock that might cause personal damages. DANGER • In case of folding electrical panels, before folding them up in order to access to the interior of the machine, it is MANDATORY to disconnect the power supply hose from the electrical voltage, THE LINE MUST ALWAYS BE FREE OF VOLTAGE for this operation.
ACHIBAei AIR-AIR PACKAGED UNITS COMPACT HORIZONTAL INVERTER DIMENSIONS MODELS 17ei – 22ei Outdoor side Indoor side MODEL 27ei Outdoor side Indoor side Outlet profile 25 mm Air filter Support point diameter Ø15 mm Male 3/4’’ indoor drain outlet Main switch Standard Power connexion inlet Electrical panel...
ACHIBAei AIR-AIR PACKAGED UNITS COMPACT HORIZONTAL INVERTER DIMENSIONS MODEL 35i Outdoor side Indoor side Outlet profile 25 mm Air filter Support point diameter Ø15 mm Male 3/4’’ indoor drain outlet Main switch Standard Power connexion inlet Electrical panel Option Male ...
ACHIBAei AIR-AIR PACKAGED UNITS COMPACT HORIZONTAL INVERTER REFRIGERATION DIAGRAM Compressor Discharge temperature 4-way valve High pressure switch Electronical expansion valve Pressure transductor Check valve Filter Suction temperature Liquid tank Indoor air temperature Suction accumulator Outdoor air temperature Outdoor coil Security valve 10.
Check that the direction of the sound level will not annoy anybody. The standard version of this equipment has been designed for installation inside a building (with a roof). Please check with Hitecsa if you plan to expose the machine to weather conditions. IOM_ACHIBA ei_17ei a 35ei_208024_200104_EN...
ACHIBAei AIR-AIR PACKAGED UNITS COMPACT HORIZONTAL INVERTER INSTALLATION SERVICE AREA (mm) 1000 mm around the equipment Indoor side Outdoor side UNIT SETTLEMENT (kg) Make sure that the equipment is levelled correctly. The bed frame shall be strong enough to support the unit weight. ...
The unit power supply shall be within 10% of volts indicated on the unit nameplate. Damage caused by the start-up of the unit with an incorrect voltage line will not be covered by the Hitecsa’s warranty. Always refer to the unit wiring diagram when completing electrical connections.
ACHIBAei AIR-AIR PACKAGED UNITS COMPACT HORIZONTAL INVERTER INSTALLATION THERMOSTAT CONNECTION Connect the TH-Tune (Mini-pGD or pGD1 as options) to the control board through the medium of a communication cable and a 230V power cable. Models 17ei, 22ei, 27ei Model 35ei ...
Check the power supply voltage. The power supply to the unit must be within 10% of the voltage level stated on the serial plate. In case of three-phases lines, make sure that the three phases are well balanced. Damages caused by the start-up of the unit with an incorrect voltage line will not be covered by the Hitecsa’s warranty. ...
ACHIBAei UNIDADES AUTONOMAS AIRE-AIRE COMPACTAS HORIZONTALES INVERTER OPERATION START-UP Make sure you have access to measuring instruments with their up-to-date calibration certificates. Thermometer, anemometer, voltmeter, hook-on meter, high and low manometer. The person/people who will complete the measuring operations or the ones who will participate in the start-up process must be qualified professionals with the valid certification according to the local regulation.
ACHIBAei AIR-AIR PACKAGED UNITS COMPACT HORIZONTAL INVERTER OPERATION INDOOR FAN TRANSMISSION ADJUSTMENT Adjust transmission so that the indoor motor consumption reaches its normal value. If consumption is below the nominal value it means that the unit air flow is too low. Motor Motor pulley Transmission...
ACHIBAei UNIDADES AUTONOMAS AIRE-AIRE COMPACTAS HORIZONTALES INVERTER MAINTENANCE WARNING! Before completing any service or maintenance operation, turn the main power switch off to avoid any personal injuries. Lock it so that anybody else than a qualified technician can switch it on. ...
ACHIBAei AIR-AIR PACKAGED UNITS COMPACT HORIZONTAL INVERTER MAINTENANCE CONSERVATION AND CLEANING Precaution! Do not use aggressive cleaning products nor varnish solvents. Avoid water penetration inside the motor or to the electronic components (e.g. through the direct contact with joints or holes of the motor), observe the protection class (IP).
ACHIBAei UNIDADES AUTONOMAS AIRE-AIRE COMPACTAS HORIZONTALES INVERTER MAINTENANCE REPAIRING OPERATIONS For all maintenance and repairing operations the current safety rules of each country have to be checked and followed. It is forbidden to do brazing repairing operations on mechanic elements such as fans, compressors, valves, etc. Use only spare parts/ wear parts / original accessories from the manufacturer of the fans.
ACHIBAei UNIDADES AUTONOMAS AIRE-AIRE COMPACTAS HORIZONTALES INVERTER APPENDIX: SAFETY DATA R410A REFRIGERANT DATA SAFETY DATA: R410A Toxicity R410 A vapours can irritate the skin and eyes. In liquid form, it can freeze skin on contact. If contact with skin occurs, Contact with Skin flush the exposed area with lukewarm water until all of the chemical is removed.
Page 24
ACHIBAei AIR-AIR PACKAGED UNITS COMPACT HORIZONTAL INVERTER Document subject to modification without prior notice. IOM_ACHIBA ei_17ei a 35ei_208024_200104_EN...