Dust Free BIO-FIGHTER 4Xtreme Installation & Operation Manual

21", 33", 45" ultraviolet light systems

Advertisement

Quick Links

GENERAL
This product is designed to help disinfect the
internal surfaces of heating, ventilation, and air
conditioning systems where the light shines.
Bacteria and viruses that are in the air stream that
pass through the system can also be reduced. The
result is an improved level of indoor air quality for
occupants and improved system hygiene.
The Bio-Fighter® emits ultraviolet(UV-C) radiation
at a frequency of 254 nanometers, which has been
proven effective in damaging the DNA of
microorganisms such as viruses, bacteria,
yeast and molds. This process either destroys
the microorganism or neutralizes its ability to
reproduce.
PO Box 519
Royse City, TX 75189
PH: 1-972-635-9564
Http://www.dustfree.com
©2021 Dust Free® • All rights reserved. • 212731-00 Rev. 3A 2/21
P/N
4Xtreme 21"
#06159
4Xtreme 33"
#06160
4Xtreme 45"
#06168
BIO-FIGHTER
4Xtreme 21", 33", 45"
Ultraviolet Light Systems
Installation & Operation Manual
FEATURES
• Reduces or prevents mold growth on HVAC coils,
allowing them to operate at peak efficiency where
the light shines. Also significantly reduces
bacteria, viruses, fungi, and yeasts on surfaces
exposed to the UV-C energy.
• NEMA 4X weatherproof enclosure.
• High output, long life UV-C lamps.
• Multi-voltage electronic ballast.
• Low maintenance and reduced costs.
INCLUDED INSIDE BOX
• Bio-Fighter® 4Xtreme ultraviolet light system
(UV-C lamp shipped separately.)
• Installation & operation manual
• UV-C warning label for duct
TOOLS REQUIRED FOR INSTALLATION
• Electric drill
• Phillips screw bit or screwdriver
• 1.125"-1.25" uni-bit or holecutter
• 3/32" drill bit
• Weatherproof conduit & conduit connector
• Weatherproof sealant
• Cotton cloth and rubbing alcohol
• Eye protection
BEFORE INSTALLING
• Read all instructions carefully. Failure to do
so could damage the equipment or cause
harm to yourself or others.
• Read all warnings and cautions.
• Only qualified technicians should perform
the installation.
®

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the BIO-FIGHTER 4Xtreme and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Dust Free BIO-FIGHTER 4Xtreme

  • Page 1 • Read all warnings and cautions. • Only qualified technicians should perform the installation. PO Box 519 Royse City, TX 75189 PH: 1-972-635-9564 Http://www.dustfree.com ©2021 Dust Free® • All rights reserved. • 212731-00 Rev. 3A 2/21...
  • Page 2: Specifications

    BIO-FIGHTER® 4XTREME INSTALLATION & OPERATION MANUAL SPECIFICATIONS Base Dimensions All Models - 11.563"L x 8"W x 4.25"H Weight: 11.56" All Models - 8.2 lbs. Electrical 120V-240V, 50/60 Hz. 3 amp-250V fuse. Listings: U.S. Patent Nos. 5,334,347, 5,817,276, 6,245,293, 6,267,924, 6,280,686, 6,313,470, 6,627,000, 6,539,727, 6,932,494, 6,550,257. 8"...
  • Page 3: Troubleshooting

    BIO-FIGHTER® 4XTREME INSTALLATION & OPERATION MANUAL SPECIAL UV-C INSTALLATION NOTES INSTALLATION GUIDELINES • Do not install in closet return grille applications. This device installs on the air handling system. • Do not expose wiring or plastic parts to UV-C light. Installation location must be at least 12"...
  • Page 4: Device Orientation

    BIO-FIGHTER® 4XTREME INSTALLATION & OPERATION MANUAL DEVICE ORIENTATION ENCLOSURE MOUNTING (Fig.3 ) The NEMA 4X enclosure of the device allows it Tape the provided mounting template at the to be installed outdoors, either horizontally or desired installation location. Use this template vertically, and remain weatherproof.
  • Page 5: Conduit Installation

    Failure to do so will void Use isopropyl alcohol and cotton cloth to wipe Dust Free® warranty. dust and fingerprints from the lamp. Gently insert the lamp into the lamp hole.
  • Page 6: Connecting The Harness

    BIO-FIGHTER® 4XTREME INSTALLATION & OPERATION MANUAL CONNECTING THE HARNESS (Fig.8 ) STRAIGHT-LAMP INSTALLATION (Fig.7 ) After lamp has been installed, attach electrical To maximize the efficiency and life of the UV-C harness. The harness connector is asymmetri- lamp, clean each lamp prior to installation. cal and can only be attached one way.
  • Page 7: Fuse Replacement

    2. Disconnect electrical service received your replacement lamps to: 3. Open the cover of the device. Allow lamp to cool 10 minutes before touching. Dust Free® Lamp Reclamation 1112 Industrial Drive 4. Disconnect the electrical connector to the Royse City, TX 75189 lamp.
  • Page 8: Limited Lifetime Warranty

    ® may not apply to you.) THE WARRANTIES SET FORTH HEREIN ARE EXCLUSIVE AND DUST FREE EXPRESSLY DISCLAIMS ALL OTHER WARRANTIES, WHETHER WRITTEN OR ORAL, IMPLIED OR STATUTORY, INCLUDING BUT NOT LIMITED TO ANY WARRANTIES OF MERCHANTABILITY, WORKMAN- SHIP , OR FITNESS FOR A PARTICULAR USE.

This manual is also suitable for:

061590616006168