Circuit Breaker Lock Open (69 Switch); Temperature Protection; Fast Vs Slow Inputs; Actuator Close And Trip Coil Continuity Monitor - ABB R-MAG Series Instructions Manual

Vacuum circuit breaker (ovb-dcm) 15.5 kv 1250/2000/3000 a
Table of Contents

Advertisement

38-929M-15A
10/15/02
1:11 PM
3.1 CIRCUIT BREAKER OPEN LOCK (69 SWITCH)
The Open Lock feature is used for service to prevent the breaker from being closed (either
locally or remotely) during maintenance. The pin locations for this binary input are KM1004
pins 11 and 12. When the circuit breaker is tripped, by operating the manual trip handle, the
breaker will go into the Open Lock mode. This prevents any future closings until the Trip
Handle is returned to the Normal Position. The Manual Trip Handle must be left in the down
position for the switch to remain open (i.e., locked open).

3.2 TEMPERATURE PROTECTION

The Temperature Protection circuit monitors the average temperature of a critical area on the
ED2.0 power supply. The output power will be linearly reduced to zero as the temperature
increases from 78 degrees C to 95 degrees C.

3.3 FAST VS SLOW INPUTS

The Slow Input needs to be active at least 10 milliseconds before the signal is considered
valid. The Fast Input only requires the input to be active for 2 milliseconds before the signal is
considered valid. However, this makes the Fast Input feature more prone to noise.

3.4 ACTUATOR CLOSE AND TRIP COIL CONTINUITY MONITOR

See Illustration 10 - Troubleshooting Guide.

3.5 WRONG POSITION AUTO TRIP

An Auto Trip command will be issued in the event the breaker does not perform a successful
close operation within 95 milliseconds after the close command is issued.
If power is removed from unit, and the Dip Switch I1004-1 is placed in the "on"
position, the breaker will automatically trip in approximately 3 minutes. Make
sure personnel and tools are clear from breaker. See Section 3.6 below.

3.6 ENERGY FAILURE AUTO TRIP

The Energy Failure Auto Trip function is selected by Dip Switch I1004-1 and will cause the
breaker to auto trip in the event the capacitor voltage falls below 49 volts. Necessary
precautions must be taken when power is removed (e.g., power removed for maintenance) as
the breaker will automatically trip if I1004-1 is in the "On" position.
Page 35