For asinterface connections

Advertisement

Available languages

Available languages

FOR ASinterface CONNECTIONS
at spool valves and solenoid valves
3 x DIN 46244 or ISO 4400 spade terminals
GENERAL
• ASinterface connections are suitable for direct control of solenoid valves and spool valves with DIN 46244 (three 6.3 x 0.8 mm spade
terminals) or ISO 4400, plug coils with maximum power ratings of 7,2 W at 24 V DC (-15 or -10%, +10%).
• Solenoid valves and spool valves can be directly integrated into the ASinterface bus.
• Electrical connection by vampire connections designed for standard flat yellow and black ASinterface cables.
• Compact design (comparable to a standard connector).
• Available with or without an additional M12 connector for one or two input/return of information sensors.
COMMUNICATION AND SPECIFICATION
Protocol
Transmission medium
Bus topology
Maximum number of connectors
Number of outputs per connector
Maximum length of bus cable
I/O refresh time
Connector addressing (subscribers)
Compatible PLCs
ELECTRICAL SPECIFICATION
ASinterface data voltage
Power voltage (black cable)
Maximum ripple
Max. connector power
Yellow cable connector consumption
24 V power connection
I/O network connection
Connection of inputs
Trigger level of one input
Signaling
Ambient temperature
Protection
CHOICE OF EQUIPMENT
Connector type
ASinterface connector
with DIN 46244 plug
(DIN 43650 industrial standard)
ASinterface connector
with ISO 4400 plug
(DIN 43650 Form A)
(
) Connector used with low power coil, consumption 1,7 W
*
NOTE: These connectors are not compatible with POSIFLOW solenoid valves
ACCESSORIES
M12 five male pins connectors for inputs (sensor return):
- with Pg7 90° elbow mono input cable for one 4 to 6 mm diameter cable, code: 881 61 927
- with Pg7 straight mono cable input for one 4 to 6 mm diameter cable,
- with straight duo cable input for two 3 to 5 mm diameter cables,
Thermoretractable ends (set of 10 pieces),
for IP65 protection at the end of the connection lines
CONNECTORS
: ASinterface
: flat black cable: 24V DC power via 2 conductors. On connecting to the power supply
unit, observe polarity, blue : - , brown : +
: flat yellow cable : data via 2 conductors
: backbone or tree
: 31 slaves
: 1 solenoid valve or spool valve per connector
: 100 m (300 m with repeater)
: 5 ms max.
: by ASinterface master via configuration software, or by pocket unit
: SIEMENS, SCHNEIDER, IFM
ASinterface gateways: Profibus - DP, Interbus-S, DeviceNet, Worldfip/FIPIO
: 31,5 V
: 24 V DC (-5%, +10%)
: 10%
: 7,2 W (0.3A)
: <150 mA
: vampire connection for ASinterface cable (black cable)
: vampire connection for ASinterface cable (yellow cable)
: M12 5 pin female connectors, power supply of inputs through black cable
: 0,36 mA
: 2 LEDs : 1 for ASinterface and 1 for coil
: -10°C to +60°C
: IP65, provided connectors and covers are correctly in place (see accessories)
Adaptation
on
coil
solenoid valves
CM22
CM5
CM25-CM30(5W)
CM6/FT - JMX
CMXX/F (1,7W)
*
These connectors are non rotatable.
on
no input
189
881 00 277
ASCO
190-192
881 00 278
ASCO
code: 881 00 330
code: 881 00 253
code: 881 57 927
NTERFACE
N˚ 21301
CODES
ASinterface connector
with M12 input
with M12 input
(Version A)
(Version B)
881 00 337
881 00 408
881 00 339
881 00 409
(Version A)
(Version B)
MS-P522
Series
881
NTERFACE
N˚21301
-GB-R2