a−HP29 P Voltage Operation Sequence
This is the sequence of operation for HP29 P" voltage
units. This sequence applies to HP29 models equipped
with either a reciprocating, or scroll compressor. The
sequence is outlined by numbered steps which correspond
to circled numbers on the adjacent diagram.
NOTE− The thermostat used may be electromechanical or
electronic.
NOTE− Transformer in indoor unit supplies power (24
VAC) to the thermostat and outdoor unit controls.
COOLING:
1 − Internal thermostat wiring
cooling mode selection, energizing the reversing valve
L1. Cooling demand initiates at Y1 in the thermostat.
2 − 24VAC energizes compressor contactor K1.
3 − K1-1 N.O. closes energizing terminal C" of compressor
(B1) and outdoor fan motor (B4).
4 − Outdoor fan motor (B4) begins immediate
operation. Scroll compressor (B1) begins
immediate operation.
5 − Reciprocating compressor (B1) begins start-up. Hard
start contactor K31 remains closed during start-up and
start capacitor C7 remains in the circuit. As the
compressor gains speed, K31 is energized. When K31
is energized, the contacts open and start capacitor C7 is
taken out of the circuit.
END OF COOLING DEMAND:
6 − Cooling
demand
de-energized.
7 − Compressor contactor K1 is de-energized.
8 − K1-1 opens and compressor (B1) and outdoor fan motor
(B4) are de-energized and stop immediately.
9 − Terminal O is de−energized when internal thermostat is
out of cooling mode, de−energizing reversing vale L1.
HP29 SINGLE-PHASE OPERATING SEQUENCE
energizes terminal O by
is
satisfied.
Terminal
FIRST STAGE HEAT:
10 − Heating demand initiates at Y1.
11 − 24VAC energizes compressor contactor K1.
12 − K1-1 N.O. closes energizing compressor and
outdoor fan motor.
13 − See step 4 or 5.
END OF FIRST STAGE HEAT:
14 − Heating demand is satisfied. Terminal Y1 is
de-energized.
15 − Compressor contactor K1 is de-energized.
16 − K1-1 opens and compressor (B1) and outdoor
fan motor (B4) are de-energized and stop
immediately.
DEFROST MODE:
17 − During
temperature drops below 35_F (2_C) or 42_(5.5_C)
(see defrost system description for specific unit dash
number) unit defrost switch (thermostat) S6 closes.
18 − Defrost control CMC1 begins timing. If defrost
thermostat (S6) remains closed at the end of the
30,60 or 90 minute period, defrost relay energizes
and defrost begins.
19 − During defrost CMC1 energizes the reversing valve
and W1 on the terminal strip (operating indoor unit on
the first stage heat mode), while de-energizing outdoor
fan motor B4.
Y1
is
20 − Defrost continues 14 + 1 minutes or until thermostat
switch (S6) opens. When defrost thermostat opens,
defrost control timer loses power and resets.
21 − When CMC1 resets, the reversing valve and W1 on the
terminal strip are de-energized, while the outdoor fan
motor B4 is energized.