If this equipment is used in a manner not specifi ed by the manufacturer, the protection provided by the equipment may be impaired. In no event will Plymovent be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
Page 4
Thus the manufacturer cannot be held responsible for any damage resulting from the application of this publication to the version actually delivered to you. This publication has been written with great care. However, the manufacturer cannot be held responsible, either for any errors occurring in this publication or for their consequences. 706304/060515/ES-90...
STOP button. The system will shut down and stay off. The ES-90 control box must be put back in Auto or Manual mode The manufacturer cannot be held liable for any damage to the for exhaust fan to start.
(skilled) 4.3.1 Terminal Block 1 using appropriate work practices. Is located in the lower left-hand corner of the ES-90 control box WARNING! and consists of incoming power electrical terminal blocks L1, L2, Electrocution hazard L3.
NOTE: Primary line voltage must not be greater or less than 8% vehicle, the BRC-MS will activate the ES-90 and turn the fan on. of rated voltage listed on voltage tap. For example, Tap 120 volt Auxiliary contact can be used to control an automatic damper.
NEC. MAINTENANCE The ES-90 requires no specifi c maintenance. TROUBLESHOOTING If the ES-90 does not function correctly, please contact your local authorized dealer/technician. SPARE PARTS Please refer to Table 1 on page 9 to view the spare parts available for the ES-90 control box.
Page 10
Table 1 Spare Parts Rated Amp Plymovent Voltage/ Overload Load for Ctrl Contactor F1 & F2*** F3*** Number Phase* Relay Box** ES-90 for 1/2 HP fan 706152 115V/1ph 935411 939058 704066 0000101409 706153 230V/1ph 935411 939041 704008 0000101409 706150 230V/3ph 1.78...
Page 11
* Voltage not to exceed 8% listed voltage. For 208V adjustment of tap on transformer maybe required (confi gured by others). ** Amp load is acquired for a Plymovent Fan running at optimal voltage. Adjustment may be required based on local voltages (to be done by proper personnel/technician).
Page 13
*If wire length is longer than distance listed, upsize to next larger AWG. Note: Guidelines are subject to change without notice. Data supplied from our primary motor supplier. Please confi rm at time of order. Plymovent assumes no liability for any electrical installation, all local, city, and the 2014 National Electric Code must be followed. This chart is a minimum standard and to be used as a guideline only.
Page 14
**2014 NEC Table 430.248 does not list 460 volt single phase motors. Note: Guidelines are subject to change without notice. Data supplied from our primary motor supplier. Please confi rm at time of order. Plymovent assumes no liability for any electrical installation, all local, city, and the 2014 National Electric Code must be followed. This chart is a minimum standard and to be used as a guideline only.